Engineering
85
06/09 AWB2723-1613en
One SmartWire-Darwin function element is used per slot.
Correspondingly more efficient function elements are used
for the combined function of a luminous command device or
for the realization of a multi-step switch.
A luminous pushbutton, which previously had to be realized
as a combination of several elements, can now be realized
simply by means of one combination element (LED indicator
+ contact element = M22-SWD-K11LEDC).
M22-SWD-KC11
This function element replaces the previous contact
elements M22-KC10/KC01. It provides a changeover contact
by means of which both a breaker and maker function can
be realized. The function element is used in combination
with M22 (pushbutton) actuators.
h
Non-used slots have to be equipped with the SmartWire-
Darwin bridge M22-SWD-SEL8-10, otherwise the
SmartWire-Darwin network will be interrupted.
h
The PCBs contain a switchable terminating resistor for the
SmartWire-Darwin network. If the surface mounting
enclosure is the last slave in the network, the terminating
resistor must be switched on.
h
You can also obtain information about terminating
resistors and on the use of the SWD link via the software
program SWD-Assist.
http://downloadcenter.moeller.net