Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
34
06/09 AWB2723-1613en
e
Connection pins
f
Adjusting slide for contactor size
g
Terminal X0-X1-X2
h
Terminal electrical enable X3-X4
i
Selector switch 1-0-A
The external device plug with an adapted SmartWire-Darwin
connecting cable is connected to the contactor module DIL-
SWD via connection
a
The communication status and switching command via the
SmartWire-Darwin system are indicated by way of a two-
colour diagnostics LED
c
(
As well as the communication signals a 24 V DC supply for
the contactor coil is also transmitted via the SmartWire-
Darwin connection cable. The integrated electronics
transfers the voltage to the connection pins
e
that are
connected to the contactor coils.
The SmartWire module for DILM is connected to the contact
bridge of the contactor by way of a ratchet slide
d
.
Feedback on the switching status of the contactor is goes
into the field bus.
In addition the status of the connected contactor can be
acquired via the switch position indicator
b
Adjustment of the SmartWire-Darwin module for DILM to
the respective contactor size is performed via the adjusting
slide for the contactor size
f
.
h
Detailed instructions on adapting the SmartWire-Darwin
device plug (SWD4-8SF2-5) to the 8-pole SmartWire-
Darwin cable are provided in chapter “Fitting external
device plugs SWD4-8SF2-5” of the manual AWB2723-
1617.