Engineering
43
06/09 AWB2723-1613en
Table 4:
Jumpers for reversing starters
In combination with the jumpers DILM12-XEV the circuit fig.
13 should be used. On the other hand, an electrical interlock
with wire jumpers should be implemented according to the
circuit fig. 14.
A manual or electrical ON or OFF command for the contactor
can take place in addition with the aid of the 1-0-A switch
i
in the device version DIL-SWD-32-002.
The switch positions are as follows:
• 1 = Contactor ON
• 0 = Contactor OFF
• A - switching command via SmartWire-Darwin
DILM7 - DILM15
DILM17 - DILM32
L1, L2 and L3 parallel
DILM12-XP2
DILM32-XRL
Phase switch L1 and L3, L2 parallel
DILM12-XR
DILM32-XRL
Electrical interlock
DILM12-XEV
-
h
Use of the 1-0-A switch for the electrical switching on or
off of the contactor is ensured only when the SmartWire-
Darwin module for DILM is supplied via the SmartWire-
Darwin connecting cable.