Section 2: Installation of IZM cassette 

cell switch

A #2 Phillips head screwdriver is recommended for this installation. 

To install the IZM cassette cell switch, proceed with the following 

five steps:

Step 1:

 Three sets of 12 wire markers are included with each 

switch assembly, allowing it to be marked for either the 

C

T

, or 

D

 

position. Depending upon the number and location of the switches 

to be used, apply the appropriate labels near the ends of the leads. 

Unused labels may be discarded.

Figure 2. Step 1

Step 2: 

Bend the gasket 90 degrees at the crease line. Fasten it 

in place between the outside wall of the cassette and the gasket 

bracket with four M6 x 10 mm thread-forming screws. A right-side 

mounting is shown. Bend the gasket the opposite way for a left- 

side mounting.

Figure 3. Step 2

Step 3: 

Insert cell switch into desired position by first sliding 

the lock to the unlocked (up) position. Install the hook feet down 

through openings, then slide switch forward so hook feet engage 

the cassette’s side wall. Slide the lock down into the locked position.

Figure 4. Step 3

1

C

C

C

Gasket

Gasket Bracket

CONNECTED 

Switch Mounts Here

TEST Switch 

Mounts Here

Hook Feet

Cell Switch

Forward

Lock

Down 

Locked 

Position

DISCONNECTED 

Switch Mounts Here

Step 4:

 Terminal blocks should be located at the end of each row, 

and should have the appropriate labels (C, D, or T, and 1 through 6, 

and 7 through 12) on them. Use the blank labels supplied with the 

terminal blocks for identification.
Wire the switch to these terminal block locations per the markings 

on the switch wires. Switch leads are terminated with “fast-on”  

connectors that will plug into the rear of the terminal blocks  

as shown.

Figure 5. Step 4

Step 5: 

If applicable, each additional switch (maximum of three) 

requires two terminal blocks or can be wired to an external source. 

Electrical accessories, such as a UVR, shunt trip or auxiliary 

switches, may limit the number of switches that can be connected 

to the breaker’s terminal block. If this is the case, the customer 

must supply an external terminal block.

Figure 6. Step 5

Terminal Locations 

7 Through 12

Terminal 

Locations 

1 Through 6

Fast-On Connectors