Eaton menvier300 Installation Manual Download Page 39

Menvier300 

Technical Specification 

 

 

Page 35 

LS 1 & 2 
(loudspeaker) 

Min impedance 16 Ohm per 
output, current consumption = 
280mA in alarm. 

Expander: 
Outputs 

Open collector transistor, 
+12VDC when inactive, 0V 
when active. 500mA max. 

Note: The current is limited by 
the amount available from the 
power supply driving the 
expander. 

KEY-KPZ01 
Outputs 

Open collector transistor, 
+12VDC when inactive, 0V 
when active, 500mA max. 

Sounder Volume Levels (at 1m) 

i-kp01 (at max volume) 

70dB 

Expander sounders 

70dB 

Expander 16 Ohm loudspeaker 

93dB 

Fuses 

The control unit has a replaceable T500mA mains 
fuse. 

Electrical Safety 

Conforms to EN60950-1. 

Other 

If you wish to connect the Menvier300 control unit 
to a PC using either the Ethernet or the USB port 
then make sure that the cables have the following 
specifications: 

Ethernet 

Cat5e patch cable, straight or 
crossed, RJ45 male plugs at 
each end, suitable for 
10/100Base-T. 

USB 

Mini-B plug for control unit end, 
USB-A for PC end. Max length 
3m.  

Radio Expander and Keypads 

Radio 

Operating frequency 
868.6625MHz Narrowband. 

  

EN 300 220-3. 

 

EN 300 330-2 

Transmitter 
range 

The range of the transmitters 
compatible with this control unit 
depends on the environment in 
which they are installed. As a 
guideline, most transmitters will 
work up 200m range in free 
space conditions. 

Compliance Statements 

The Menvier300 is compliant with EN50130-5 
environmental class II. 

The Menvier300 is suitable for use in systems 
designed to comply with PD 6662: 2010 at grade 
3. 

When installed correctly the Menvier300 is 
capable of compliance with EN50131 at Grade 3. 

To maintain Grade 3 the Menvier300 must be 
fitted with a communicator of level ATS4 or above. 

When fitted with radio devices the Menvier300 is 
capable of compliance with EN50131 at Grade 2. 

The i-sd02 is compliant with EN50136-1 as an 
ATS2 communicator. 

The i-sd02 may be used as a supplementary 
communicator at Grade 3.  

At Grade 2 the i-sd02 provides a compliant 
communicator for the Menvier300 provided that: 

a)  It is installed in accordance with the 

installation instructions. 

b)  The connected PSTN is functioning normally. 

When fitted with an i-sd02 this product provides 
options A, B and C at Grade 2 as noted in Table 
10 of EN50131-1:2006+A1:2009. 

If the installer selects a non-compliant 
configuration then they must remove or adjust 
compliance labelling 

Third party testing carried out by Anpi. 

Compatible Equipment 

HUD 

705rEUR-00 

Two button HUD (single 
channel, top button is 
disabled) 

706rEUR-00 

Two button HUD/tilt switch 
transmitter 

710rEUR-00 

Two button HUD 

726rEUR-50 

Long range hand held HUD 

726rEUR-60 

Short range hand held HUD 

Detectors 

713rEUR-00 

Pet tolerant PIR 

714rEUR-00 

PIR Transmitter (Small case) 

720rEUR-00 

Smoke Detector Transmitter 

734rEUR-00/01 

CC/FSL Door Contact 
Transmitter (white) 

734rEUR-05/06 

CC/FSL Door Contact 
Transmitter (brown) 

738rEUR-00/04 

Spyder shock sensor 
(white/brown) 

739rEUR-50 

Sentrol glass break detector 

Summary of Contents for menvier300

Page 1: ...Menvier300 Security System Installation Guide Issue 3...

Page 2: ...ment but will not damage the equipment Caution Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cau...

Page 3: ...19 Step 5 Connect Control Unit to Mains 19 Mains Cabling 19 Step 6 Connect Wired Zones 20 Four Wire Closed Circuit Connections 20 Two Wire Closed Circuit Connections 20 Fully Supervised Loop Connectio...

Page 4: ...Menvier300 Page iv This page is intentionally blank...

Page 5: ...s control unit is designed and approved to be used as part of a Security Grade 3 system The control unit is also approved to operate as part of a Security Grade 2 system If you install any radio devic...

Page 6: ...rom a PC or laptop connected to the Ethernet port on the control unit PCB The control unit contains a web page server and you can use any web browser to see a complete version of the Installer menu Pl...

Page 7: ...ition can all affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for...

Page 8: ...conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the Menvier300 its expanders and keypads have been tested for Electr...

Page 9: ...ctors 11 RS485 terminator 12 Engineering keypad connector 13 Zone output and Aux power connectors 14 Kickstart pins Batt 1 only 15 Battery connectors two of 16 20Vac connector 17 USB socket Mini B Fig...

Page 10: ...open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing Fig...

Page 11: ...ly push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the front out from the back...

Page 12: ...Y EP Terminals for zones 4 Sounder volume control 5 Connector for control unit data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing 6b LED functions and RS485 bus termi...

Page 13: ...ker connectors 19 Outputs Figure 15 EXP 10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper swi...

Page 14: ...able front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Louds...

Page 15: ...charge required by the example system for PD6662 Grade 3 requirements Note All current drawn from the Aux terminals 12V and 14 4V must be included in the overall calculation CAUTION Ensure that the sy...

Page 16: ...e only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices on the end of each arm If there ar...

Page 17: ...V 4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Reducing Voltage Drop Method 1 Double up t...

Page 18: ...and mark the position of the case Also mark the position where the lid back tamper bracket touches the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 21...

Page 19: ...s the KEY EP or prox readers used by other systems for example access control systems If you mount prox readers closer together than one meter including on the other side of walls then the two prox re...

Page 20: ...backlights by fitting links over the BRIGHT jumper on the keypad pcb see 1b in Figure 12 or 6b in Figure 14 Jumper OFF The keypad backlights glow at normal intensity Jumper ON The keypad backlights g...

Page 21: ...cal programming mode and save your changes see below To Disable Enable the Status OK LED 1 Enter Local Programming mode MENU ABCD 2 Press repeatedly until the display shows MENU STATUS OK LED 3 Press...

Page 22: ...ou do so then the prox readers will interfere and be unable to read tags Opening the External Prox Reader To open the external prox reader see Figure 27 1 Undo the single retaining screw 2 Tilt the ed...

Page 23: ...nders Addressing Expanders The control unit assigns addresses to all devices connected to the bus cable You can start this process off from the Installer Menu during the initial power up See Initial P...

Page 24: ...igure 35 shows the wiring for CCL zones on the KEY KPZ01 Figure 35 KEY KPZ01 CCL Zone Wiring Two Wire Closed Circuit Connections With version 4 02 and higher software you can connect two wire CCL dete...

Page 25: ...examples Figure 39 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resistor values for the control unit in Installer Menu System Options Wired Zone Type To select the resistor values for...

Page 26: ...By default the terminal is CC If you program the TR terminal as FSL then make sure you connect a 2k2 resistor in series with the wire to the sounder Note If you do not wish to connect a wired externa...

Page 27: ...or 4k7 4k7 FSL wiring and a single core of standard 6 core alarm cable Fit EITHER a 2k2 resistor if using 2k2 4k7 FSL OR a 4k7 resistor if using 4k7 4k7 FSL Do not use any other FSL resistor combinat...

Page 28: ...lt is absent Remote Reset Tell Back Input This input is marked RR is designed to allow a plug by communicator to indicate to the control unit that the user can reset the system after a system tamper T...

Page 29: ...sounders internal loudspeakers and wired sirens MAY give an alarm tone If you are working at the top of a ladder make sure that the sudden noise does not startle you and cause a fall 1 Apply mains pow...

Page 30: ...one and shows its assigned address on the two digit LED display Replace the lid NOTE 1 DO NOT request a bus address from two different devices at the same time 2 EXP R30 expanders take three bus addre...

Page 31: ...nt store If you remove all power BEFORE you leave the Installer Menu then the control unit will lose your changes Note that this does not apply if you restore Factory Defaults that change takes place...

Page 32: ...d to restore the tamper switch The display shows the time and date for example 9 Key in the default user 01 code to silence the sounders The display shows 10 Enter Installer Menu and then leave it aga...

Page 33: ...see Chapter 5 option to a carry out a walk test of the detectors b test the operation of any other peripherals Program the System Program the system to suit user requirements Page 30 is a summary of t...

Page 34: ...Edit Exception Delete Exception 4 SYSTEM OPTIONS Wired Zone type Panel Zones All Zones User Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable Use...

Page 35: ...ears only when Dynamic Test call disabled 18 Appears only when Report Type Fast Format AND Confirmation Mode Basic 19 Shows None if no module fitted 20 Must be activated by a Eaton s Security Business...

Page 36: ...wish to find the location of any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from it...

Page 37: ...ents 1 500 mandatory events 500 non mandatory Stored in EEPROM memory available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains suppl...

Page 38: ...t consumption of the control unit and each device that can be fitted to it CIE power requirement 140mA min 220mA max i kp01 power requirement 30mA backlight off 45mA 65mA backlight norm bright 60mA in...

Page 39: ...nvironmental class II The Menvier300 is suitable for use in systems designed to comply with PD 6662 2010 at grade 3 When installed correctly the Menvier300 is capable of compliance with EN50131 at Gra...

Page 40: ...output and terminals for external prox reader Setting Unsetting Fobs FOB 2W 4B Two way keyfob i fb01 Four button remote control 727rEUR 00 Four button remote control with encrypted code HUD function n...

Reviews: