Maintenance, testing, and operating conditions
MAGNUM PXR PRODUCT GUIDE
PA013006EN September 2022 www.eaton.com
6
Altitude factors
All Magnum breakers can be applied at their full voltage
and current ratings up to a maximum altitude of 2000
meters above sea level. When installed at higher altitudes,
the ratings are subject to correction factors. Short circuit
current is not affected as long as the voltage is rated in
accordance with the information shown in the
Table 30
.
Table 30. Altitude rating factors
Altitude
(meters)
Voltage
correction
Current
correction
2000
1.000
1.000
2150
0.989
0.998
2300
0.976
0.995
2450
0.963
0.993
2600
0.950
0.990
2750
0.933
0.987
2900
0.917
0.983
3050
0.900
0.980
3200
0.883
0.977
3350
0.867
0.973
3500
0.850
0.970
3650
0.833
0.967
3800
0.817
0.963
3950
0.800
0.960
5000
0.700
0.940
Test bus configuration
The bus bar size examples shown here are those specified
by ANSI, IEC 947-1 and/or used by Eaton in their breaker
type testing. They are for 3 meter long bus bar with the
faces vertical and painted flat black. For other bus bar
configurations, larger bus bar sizes may be required or
the breaker may have to be de-rated. Refer to the tables
presented earlier in this section for de-rating information at
higher ambient temperatures.
Table 31. ANSI busbar sizes and quantities
Maximum
services current
amperes
(40ºC ambient)
Recommended busbar quantities and sizes
(in)
(mm)
800
(1) .25x3.0
(2) 5x50
1200
(2) .25x3.0
(2) 5x80
1600
(2) .25x3.0
(2) 5x100
2000
(3) .25x3.0
(3) 5x100
2500
(4) .25x3.0
(4) 5x100
3200
(3) .25x6
(3) 10x100
4000
(4) .25x6
(4) 10x100
5000
(5) .25x6
(5) 10x100
6000
(6) .25x6
(6) 10x100
Figure 85. Bus bar size examples