32
PXR trip unit and communication modules
MAGNUM PXR PRODUCT GUIDE
PA013006EN September 2022 www.eaton.com
3
Table 7. Enhanced protection settings (PXR 25 only)
Protection
Units
Settings
ANSI 59
Voltage Protection
Over Voltage Pickup
Volts
180 to 720 in steps of 1
Over Voltage Delay
Seconds
1 to 300 in steps of 1
ANSI 27
Under Voltage Pickup
Volts
60 to 670 in steps of 1
Under Voltage Delay
Seconds
1 to 300 in steps of 1
ANSI 47
Voltage Unbalance Pickup
% Volts
5 to 25 in steps of 1
Voltage Unbalance Delay
Seconds
1 to 300 in steps of 1
ANSI 46
Current Protection
Current Unbalance Pickup
% Amps
5 to 25 in steps of 1
Current Unbalance Time
Seconds
1 to 300 in steps of 1
ANSI 78V
Phase Loss Pickup
% Amps
75
Phase Loss Delay
Seconds
1 to 240 in steps of 1
ANSI 32R
Power Protection
Reverse Power Pickup
kW
1 to 65,500 in steps of 1
Reverse Power Delay
Seconds
1 to 300 in steps of 1
PXR trip unit module catalog numbers
Table 8
below lists the available PXR trip unit field-installable kits and their respective features.
Table 8. PXR trip unit field-installable kits
Trip unit
Trip unit catalog number
Breaker catalog
digit 13, 14
Protection
ARMS
Communication
Metering
PXR 20
PXR20VN30LNNC
2A
LSI
N
Adapter Module (CAM)
Current
PXR20VN30LGNC
2C
LSIG
N
Adapter Module (CAM)
Current
PXR20VN30LNAM
2H
LSI
Y
Modbus RTU & CAM
Current
PXR20VN30LGAM
2F
LSIG
Y
Modbus RTU & CAM
Current
PXR 25
PXR25VN30LNAM
2Q
LSI
Y
Modbus RTU & CAM
Current, voltage,
power, energy
PXR25VN30LGAM
2S
LSIG
Y
Modbus RTU & CAM
Current, voltage,
power, energy
ote:
N
CAM modules are not included with the breaker and are ordered separately.
Magnum DS digitrip to Magnum PXR equivalency
Refer to
Table 9
below for existing digitrip options and their equivelent PXR trip unit offering. The catalog characters 13
and 14 in the full 25-character catalog string indicate the trip unit the breaker is equipped with.
Table 9. Conversion of Magnum DS Digitrip Catalog Characters to Magnum PXR (characters 13 and 14)
Digitrip trip unit
PXR trip unit
Catalog characters
Description
Catalog characters
Description
Features
52
520 LSI
2A
PXR 20 LSI
Base unit - includes display and 24 Vdc aux
M_
520M LSI
2A
PXR 20 LSI
5G
520 LSIG
2C
PXR 20 LSIG
Adds ground fault (GF)
M_
520M LSIG
2C
PXR 20 LSIG
C_
520MC LSI
2H
PXR 20 LSI
Base + ARMS, Modbus
C_
520MC LSIG
2F
PXR 20 LSIG
Base GF + ARMS, Modbus
1_
1150 LSI
2Q
PXR 25 LSI
Includes Arms, Modbus
1_
1150 LSIG
2S
PXR 25 LSIG
Includes GF, ARMS, Modbus