04/10 MN04020001Z-EN
Mains contactors
159
Mains contactors
h
The mains contactor shown here considers the input-side
rated operating current I
LN
of the frequency inverter
without a mains reactor. Their selection is based on the
thermal current (AC-1).
h
Caution!
Debounced inputs may not be used in the safety
circuit diagram.
The inching range is not permitted via the mains contactor
(Pause time
f
60 s between switching off and on).
h
Technical data on the mains contactors can be found in
the main catalog HPL, Contactors DILEM and DILM7.
Figure 117: Mains contactor at single-phase connection
DILM12-XP1
P1DILEM
DILM
DILEM
DILM12-XP1
P1DILEM
2
3
5
4
6
A1
A2
1
13
14
Part no.
M-Max
TM
Rated voltage
Rated input
current without
mains reactor
Part no. of the allocated
mains contactor
Conventional
thermal current
(DILEM, DILM7)
I
th
= I
e
AC-1 at
+50 °C
(50 Hz)
(60 Hz)
U
LN
U
LN
I
LN
I
N
I
N
[A]
[A]
[A]
MMX11AA1D7N0-0
1 AC 120 V
1 AC 120 V
9.2
DILM7 + DILM12-XP1
20
21
MMX11AA2D4N0-0
1 AC 120 V
1 AC 120 V
11.6
DILM7 + DILM12-XP1
20
21
MMX11AA2D8N0-0
1 AC 120 V
1 AC 120 V
12.4
DILM7 + DILM12-XP1
20
21
MMX11AA3D7N0-0
1 AC 120 V
1 AC 120 V
15
DILM7 + DILM12-XP1
20
21
MMX11AA4D8N0-0
1 AC 120 V
1 AC 120 V
16.5
DILM7 + DILM12-XP1
20
21
MMX12AA1D7…
1 AC 230 V
1 AC 240 V
4.2
DILEM-10
1)
DILM7
20
21
MMX12AA2D4…
1 AC 230 V
1 AC 240 V
5.7
DILEM-10
1)
DILM7
20
21
MMX12AA2D8…
1 AC 230 V
1 AC 240 V
6.6
DILEM-10
1)
DILM7
20
21
MMX12AA3D7…
1 AC 230 V
1 AC 240 V
8.3
DILEM-10
1)
DILM7
20
21
MMX12AA4D8…
1 AC 230 V
1 AC 240 V
11.2
DILM7
21
MMX12AA7D0…
1 AC 230 V
1 AC 240 V
14.1
DILM7
21
MMX12AA9D6…
1 AC 230 V
1 AC 240 V
15.8
DILM7
21
MMX32AA1D7N0-0
3 AC 230 V
3 AC 240 V
2.7
DILEM-10
20
MMX32AA2D4N0-0
3 AC 230 V
3 AC 240 V
3.5
DILEM-10
20
MMX32AA2D8N0-0
3 AC 230 V
3 AC 240 V
3.8
DILEM-10
20
MMX32AA3D7N0-0
3 AC 230 V
3 AC 240 V
4.3
DILEM-10
20
MMX32AA4D8N0-0
3 AC 230 V
3 AC 240 V
6.8
DILEM-10
20
MMX32AA7D0N0-0
3 AC 230 V
3 AC 240 V
8.4
DILEM-10
20
MMX32AA9D6N0-0
3 AC 230 V
3 AC 240 V
13.4
DILM7
21
1) The use of paralleling links (P1DILEM) is suggested when using the DILEM-10 for even flow path loads.
Summary of Contents for M-Max series
Page 8: ...04 10 MN04020001Z EN 4...
Page 12: ...04 10 MN04020001Z EN 8...
Page 58: ...04 10 MN04020001Z EN 54...
Page 66: ...04 10 MN04020001Z EN 62...
Page 138: ...04 10 MN04020001Z EN 134...
Page 150: ...04 10 MN04020001Z EN 146...
Page 196: ...04 10 MN04020001Z EN 192...