background image

 

 

                                   

                                                                                                                                                                                                         

 

LMR Plus Electric Fire Pump Controllers 

 

July 2011 

For more information visit:

 www.chfire.com

 PS05805008K/E 

Fire Pump Controllers 

1-2 

Features 

7. Interlock 

On 

8. Low 

Pressure 

9.  Auto Shutdown Enabled 
10.  Programmable LED #1 

C.  The controller shall be supplied with ten (10) red 

alarm LED’s to indicate the following: 
1. Phase 

Reversal 

2. Phase 

Failure 

3.  Fail to Start 
4. Undervoltage 
5. Overvoltage 
6.  Low Room Temperature 
7. Locked 

Rotor 

Trip 

8.  Low Suction Pressure 
9.  Source 2 Disconnected 
10.  Programmable LED #2 

D.  The microprocessor logic board shall be available 

with: 
1.  A USB port for transference of message history, 

controller status, diagnostics, and statistics and 
the ability to update firmware. 

2.  An optional Ethernet port for direct connection to 

a computer for data transfer. 

3.  An optional RS485 Serial port for communica-

tion to various external software programs. 

E.  The controller shall be available with an embedded 

web page to allow viewing of the controllers' current 
status, data values, programmed set points, and his-
tory. 

F.  A Fail-to-Start alarm shall occur if the motor control-

ler sees less than 20% of the motor full load amps af-
ter an adjustable time delay of 1-90 seconds. 

G.  Locked rotor protection shall be provided.  After a trip 

condition and restoration of power, the LCD display 
shall indicate “LOCKED ROTOR TRIP”. 

H.  A sequential start timer and weekly test timer shall 

be provided as standard. 

I. 

A restart time delay of two (2) seconds shall be pro-
vided to allow the residual voltage of the motor to 
decay prior to re-starting the motor.  In the event that 
the pump motor continues to run after a request to 
stop, then the controller must display a fail to stop 
message to indicate this condition. 

J. 

Overvoltage (5-20%) and undervoltage (5-30%) 
sensing and alarming shall be provided as standard. 

K.  The controller shall be supplied with interlock and 

shutdown circuits as standard.  A flashing green LED 
shall indicate an interlock on condition.  

L.  Where shutdown of the pump(s) due to low suction 

pressure is required, it shall be accomplished without 
the addition of a separate panel or enclosure.  The 
LCD display shall indicate low suction shutdown.  
Resetting of the condition shall be automatic or ma-
nual as selected by the user. 

M.  Means shall be provided to test the operation of all 

LED’s to ensure their functionality. 

 

7. Programming 

Menu 

A.  The programming menu shall have the ability to ena-

ble an entry password. 

B.  The programming menu shall be limited to two (2) le-

vels of password protection. 

C.  The controller shall have three (3) languages as a 

standard, English, French, and Spanish, with the 
ability to add a fourth language. 

D.  The programming menu shall be grouped into 6 main 

menu headings as follows: 
1. Regional 

Settings 

2. Pressure 

Settings 

3. Timer 

Values 

4.  Alarm Set points 
5. Input/Output 

Menu 

6. System 

Configuration (password protected) 

8. Pressure 

Sensor 

A.  A solid-state 4-20mA pressure sensor shall be pro-

vided. The pressure Start and Stop points shall be 
adjustable in increments of one (1) PSI.  A low pres-
sure pre-alarm, indicated with a flashing green LED, 
shall denote a potential pump starting condition and 
will remain lit once the pump has started to indicate 
the starting cause. 

9. Custom 

Inputs/Outputs 

A.  The controller shall come standard with nine (9) fu-

ture inputs, two (2) future LED indicators, and one (1) 
future output, with the ability to add up to another 8 
outputs via optional relay boards. 

B.  The user shall be able to program the future in-

puts/outputs through the main programming menu. 

C.  The inputs shall be selectable based on the following 

criteria: 
1.  User selected message or thirteen (13) prede-

termined messages. 

2.  Energize the common alarm relay when the in-

put is received. 

3.  Link to a future relay and/or LED indicator. 
4.  Alarm latched until reset. 
5.  Normally open or closed input. 
6. On-delay 

timer. 

D.  The LED indicators shall be selectable based on the 

following criteria: 
1.  Indication based on a minimum of twelve (12) 

predetermined alarms or a custom input. 

E.  The future relays shall be selectable based on the 

following criteria: 
1.  Output based on a minimum of twenty-seven 

(27) predetermined alarms, controller status or a 
custom input. 

2.  Latched until reset. 
3.  Energized under normal conditions. 
4.  On or off delay timer on the output. 

 
 

Summary of Contents for LMR PLUS

Page 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Page 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Page 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Page 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Page 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Page 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Page 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Page 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Page 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Page 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Page 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Page 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Page 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Page 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Page 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Page 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Page 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...

Reviews: