Electric Fire Pump Controllers & Transfer Switches
Part Number / Options Selection Guide

FD / FT & FDF / FTF (Foam) - Electric Fire Pump Controllers

For more information visit: 

www.chfire.com

PA05805031K

Electric Fire Pump Controllers & Transfer Switches

March 2014

N. Y. C.

APPROVED

 

U.B.C and C.B.C

Must Be Installed Per Applicable Code
and Manufacturers Recommendations

SEISMIC QUALIFIED

Part Number / Options Selection Guide

LMR

PLUS 

PLUS 

FD / FDF
FT / FTF

 FD / FDF

 = Stand Alone Controller

 FT / FTF 

Controller c/w Transfer Switch

A

- Built-in Alarm System

B

- Alarm Bell

  20

 =  Limited Service

C1

- Extra Contacts "Pump Run" (Two Form-C)

  30

 =  Across the Line

C2

- Extra Contacts "AC Power Failure" (Two Form-C)

  40

 =   Part Winding

C3

- Extra Contacts "Phase Rev." (Two Form-C)

  50

 =   Primary Resistor

C4

- Remote Contacts (2 Form C) Low Reservoir

  60

 =   Autotransformer

C5

- Remote Contacts (2 Form C) High Reservoir

  70

 =   Wye Delta (Star-Delta) Open

COM

- Communications Option

  80

 =   Wye Delta (Star-Delta) Closed

CX

- Extra Contacts (Two Form-C; Specify Function)

  90

 =  Soft Start

E1

- NEMA 3R - Raintight Enclosure

E2

- NEMA 4 - Watertight Enclosure 

E3

- NEMA 12 - Industrial Dust Tight Enclosure

E5

- NEMA 4X - 304 Stainless Steel Enclosure  

E8

- Tropicalization

5

20

50

300

500

E9

- NEMA 4X - Painted Steel 

7.5

25

60

350

550

E10

- NEMA 4X - 316 Stainless Steel Enclosure 

10

30

75

400

600

EX

- Export Crating

15

40

100

450

650

F2

- Floor Stand - 2 Inch Height**

H

- High Withstand Rating (refer to tables)

I

- Intermediate Withstand Rating (refer to tables)

LX

- Extra Light (Specify Description)

P5

- Proof Pressure Switch - ALCO 15-290 PSI

P7

- Low Suction Pressure Switch

P8

- Low Suction Shutdown (Requires P7)

  A 

 =   208V - 60HZ

P10

- Pressure Transducer - Sea Water Rated

  B 

 =   240V - 60HZ 

  L1 

  =  English

P13

- Externally Mounted Pressure Transducer**

  C 

 =   380V - 50HZ

  L2

   =  French

R1

- Space Heater (120 / 220V)

  D 

 =   480V - 60HZ

  L4

   =  Italian

R2

- Space Heater c/w Thermostat

   E 

 =   600V - 60HZ

  L5

   =  Spanish

R3

- Space Heater c/w Humidistat

   F 

 =   415V - 50HZ

  L6

   =  Portuguese

R4

- Low Pump Room Temperature Switch 

  H 

 =   380V - 60HZ

 

 L7 

  =  Chinese

R5

- Space Heater (Externally powered - 120V)

   J 

 =   400V - 50HZ

  L8 

  =  Polish

USB

- Externally Mounted USB Port

  K 

 =   400V - 60HZ

  L9

   =  Dutch

X1

- Printer

  G2

 =

  L11

 =  Turkish

X2

- 4 Inch Chart Recorder ( 10 - 300 psi fresh water)

** Not available for NEMA 4 or NEMA 4X units.

* Only available on Limited Service Controllers

  240V 60 HZ                             
Single Phase*

Language

Starting Type

Model

Options

* Higher Horsepowers not available on all 
models.  Consult Factory for pricing.

Voltage

125

250

200

150

700

Horsepower

Summary of Contents for LMR PLUS

Page 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Page 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Page 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Page 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Page 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Page 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Page 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Page 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Page 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Page 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Page 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Page 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Page 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Page 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Page 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Page 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Page 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...