background image

7

Instruction  Leaflet  

IL29C092E

Effective November 2013

Installation Instructions for KD, HKD, KDC, CKD,

CHKD, Circuit Breakers with Digitrip OPTIM

Trip Unit and Powernet and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

Indicator

Color.

Red

On

Indicator

Reset

Figure 3-1 Circuit Breaker

breaker interface module.  If IMPACC Series III software

is part of the system, this too can be used to set the trip 

unit settings.  Refer to the user manuals for details.

3-0

MANUAL OPERATION

Manual operation of the circuit breaker is controlled by

the circuit breaker handle and the PUSH-TO-TRIP but-

ton in the trip unit.  The circuit breaker handle has three

positions, two of which are shown on the cover with

raised lettering to indicate ON and OFF.  On the handle, 

ON, OFF, and trip are also shown by a color-coded strip 

for each circuit breaker handle position: red for ON,

white for tripped, and green for OFF (see Figure 3-1).

Circuit Breaker Reset

After a trip operation, the circuit breaker is reset by mov-

ing the circuit breaker handle to the Reset (extreme 

OFF) position. It is not necessary to press the reset

button before resetting the breaker.  The reset button 

affects only the cause of trip indicator LED’s. It does not 

affect the operation of the circuit breaker itself.

No circuit breaker should be reclosed until the

cause of trip is known and the situation rectified. 

PUSH-TO-TRIP Button

The PUSH-TO-TRIP button operates the circuit breaker

tripping function and may be used to periodically exer-

cise the operating mechanism.  The button is designed

to be operated by a small screwdriver. 

4-0

INSPECTION AND FIELD TESTING

Series C molded case circuit breakers are designed to

provide years of almost maintenance-free operation. 

The following procedure describes how to do a limited 

amount of field inspection and testing of a circuit break-

er.

Inspection

Circuit breakers in service should be inspected periodi-

cally. The inspection should include the following

checks 4-1 through 4-7.

WARNING

THE VOLTAGES IN ENERGIZED EQUIPMENT CAN

CAUSE SEVERE PERSONAL INJURY OR DEATH.

BEFORE INSPECTING THE CIRCUIT BREAKER IN

AN ELECTRICAL SYSTEM, MAKE SURE THE CIR-

CUIT BREAKER IS SWITCHED TO THE OFF POSI-

TION AND THAT THERE IS NO VOLTAGE PRESENT 

WHERE WORK IS TO BE PERFORMED.

SOME COMMERCIAL CLEANING AGENTS WILL

DAMAGE THE NAMEPLATES OR MOLDED PARTS. 

MAKE SURE THAT THE CLEANING AGENTS OR

SOLVENTS USED TO CLEAN THE CIRCUIT BREAK-

ER ARE SUITABLE FOR THE JOB.

4-1.

Remove dust, dirt, soot, grease, or moisture from

the surface of the circuit breaker using a lint-free dry

cloth, brush, or vacuum cleaner.  Do not blow debris into

Summary of Contents for KD

Page 1: ...anual Operation 7 4 Inspection and Field Testing 7 Effective November 2013 Supersedes IL29C092D 08 11 Instruction Leaflet IL29C092E Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers w...

Page 2: ...dations Electrotechnical Commision Recommendations No warnings and cautions relating to the safety of person IEC 157 1 The OPTlM 750 and 1050 K Frame circuit nel and equipment as well as all general a...

Page 3: ...CAUTION WHEN REMOVED AND REINSTALLED THREAD FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE CARE SHOULD BE TAKEN EVERY TIME A THREAD FORIVIING SCREW IS USEDTO ENSURE THE SCREW STARTS IN THE...

Page 4: ...crew Terminal Mounting Screw Figure 2 1 Terminal lnstallation 2 3 Pole Breakers 4 Pole Breaker Circuit Figure 2 2 Circuit Breaker Mounting Bolt Drilling Plans Circuit Breaker Handle Figure 2 3 Circuit...

Page 5: ...iring connections are made on the removable male plug of the terminal block 4 If the customer requires the interlock feature in their system then the removal of the jumper between positions 2 3 is req...

Page 6: ...RSONAL INJURY MAIN TAIN ORIGINAL ELECTRICAL CLEARANCE AND CREEPAGE SPACINGS AT TERMINATIONS 2 12 Connect the control wires and power wires to their appropriate locations on the male plug of the termin...

Page 7: ...oes not affect the operation of the circuit breaker itself No circuit breaker should be reclosed until the cause of trip is known and the situation rectified PUSH TO TRIP Button The PUSH TO TRIP butto...

Page 8: ...ult Trip Units Code Requirements The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be cond...

Page 9: ...AUTION GROUND FAULT TEST RECORD FORM Ground Fault Test Records should be Retained by Those in Charge of the Building s FIELD TESTING SHOULD BE USED FOR FUNCTION AL TESTING AND NOT FIELD CALIBRATION OF...

Page 10: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 11: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 12: ...information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eat...

Reviews: