Instruction  Leaflet  

IL29C092E

Effective November 2013

Installation Instructions for KD, HKD, KDC, CKD

CHKD, Circuit Breakers with Digitrip OPTIM

 

Trip Unit and Powernet and/or Zone Interlock

EATON CORPORATION

 www.eaton.com

Table 2-1 Terminal Types

Terminal Terminal Screw

AWG

Wire

Torque

Cat.

No.

Material

Head

Wire

Wire

Type

Value

Body 

Type 

Range 

Range 

Ib-in

Aluminum  Socket 

35-185

275 (31)

Aluminum Socket

120-240

375 (42)

Socket

275 (31)

K  Aluminum  Socket

275 375

or 

or 

(31

375 (42) 

Socket

240-300

550 (62)

Socket

35-185 Cu Only 275 (31)

Copper

Socket

120-240

375 (42)

Copper

Socket

Cu Only 275 (31)

CAUTION

WHEN ALUMINUM CONDUCTORS ARE USED, THE

APPLICATION OF A SUITABLE JOINT COMPOUND

IS RECOMMENDED TO REDUCE THE POSSIBILITY

OF TERMINAL OVERHEATING. OVERHEATING

CAN CAUSE NUISANCE TRIPPING AND DAMAGE 

TO THE CIRCUIT BREAKER.

Table

2-2

Rating Plugs

2-11. When step-type terminals (TA400K, TA401K,  

TA402K or T400K) are used, terminal shields (supplied 

with terminals) must be installed on the circuit breaker 

(Figure 2-4).  Warning label supplied with the kit must 

be attached to the circuit breaker cover. 

WARNING

HAZARDOUS VOLTAGE CONDITIONS CAN CAUSE

DEATH OR SEVERE PERSONAL INJURY.  MAIN-

TAIN ORIGINAL ELECTRICAL CLEARANCE AND

CREEPAGE SPACINGS AT TERMINATIONS.

2-12. Connect the control wires and power wires to their

appropriate locations on the male plug of the terminal

block, see Figure 2-5. Control power is necessary if 

IMPACC communication is required. 

2-13. Install an appropriate rating plug, see Table 2-2.

2-14. Plug in the hand held Digitrip OPTIMIZER into the

programming port and set the INCOM address.  Then 

set the various trip unit current settings using the OPTI-

MIZER, or when INCOM is available, use the circuit

Connect line and load conductors and accessory 

leads.

When a dual conductor terminal (Catalog 

No.

TA402K, TA401K, TA400K or T400K is installed on

the circuit breaker and 

a single conductor is used, 

the conductor should be installed in the terminal 

opening nearest to the circuit breaker terminal 

mounting  conductor. 

2-8. Install the supplied neutral current sensor in the

neutral pole of a four-wire system, see Figure 2-6.

2-9. After the circuit breaker is installed, check all 

mounting hardware and terminal connecting hardware 

for correct torque loading.  Torque values for line/load 

terminals are given in Table 2-1 and on the circuit

breaker nameplate. 

2-1 0. If required, install line terminal cover on circuit

breaker cover with mounting slots provided. 

13

tapped

Figure

2-6

Neutral Sensor Dimensions

Summary of Contents for KD

Page 1: ...anual Operation 7 4 Inspection and Field Testing 7 Effective November 2013 Supersedes IL29C092D 08 11 Instruction Leaflet IL29C092E Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers w...

Page 2: ...dations Electrotechnical Commision Recommendations No warnings and cautions relating to the safety of person IEC 157 1 The OPTlM 750 and 1050 K Frame circuit nel and equipment as well as all general a...

Page 3: ...CAUTION WHEN REMOVED AND REINSTALLED THREAD FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE CARE SHOULD BE TAKEN EVERY TIME A THREAD FORIVIING SCREW IS USEDTO ENSURE THE SCREW STARTS IN THE...

Page 4: ...crew Terminal Mounting Screw Figure 2 1 Terminal lnstallation 2 3 Pole Breakers 4 Pole Breaker Circuit Figure 2 2 Circuit Breaker Mounting Bolt Drilling Plans Circuit Breaker Handle Figure 2 3 Circuit...

Page 5: ...iring connections are made on the removable male plug of the terminal block 4 If the customer requires the interlock feature in their system then the removal of the jumper between positions 2 3 is req...

Page 6: ...RSONAL INJURY MAIN TAIN ORIGINAL ELECTRICAL CLEARANCE AND CREEPAGE SPACINGS AT TERMINATIONS 2 12 Connect the control wires and power wires to their appropriate locations on the male plug of the termin...

Page 7: ...oes not affect the operation of the circuit breaker itself No circuit breaker should be reclosed until the cause of trip is known and the situation rectified PUSH TO TRIP Button The PUSH TO TRIP butto...

Page 8: ...ult Trip Units Code Requirements The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be cond...

Page 9: ...AUTION GROUND FAULT TEST RECORD FORM Ground Fault Test Records should be Retained by Those in Charge of the Building s FIELD TESTING SHOULD BE USED FOR FUNCTION AL TESTING AND NOT FIELD CALIBRATION OF...

Page 10: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 11: ...n Leaflet IL29C092E Effective November 2013 Installation Instructions for KD HKD KDC CKD CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and or Zone Interlock EATON CORPORATION www ea...

Page 12: ...information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eat...

Reviews: