Eaton - Lighting Systems iLight Product Series - UIG-2 73-898-00 IM8840 Iss.02 4
Outputs
4 LED Outputs
A. LED outputs drive remote indicators
B. Each output provides a 10mA supply
capable of driving LED’s up to a forward drop
of 6.7V.
C. Indicates input status when opto-isolated
input are configured for scene selection
D. Can also be configured for indication of
other functions
E. All LED outputs wire with 2 part connectors
with screw terminals. Wire sizes 4mm2 (12
AWG) to 0.25mm2 (24 AWG).
Functions
A. 16 sequences of up to 128 steps each
B. 4 room joins with up to 3 partitions each
Ambient atmosphere requirements
Temperature: 0°C to +40°C (32°F to 104°F)
Humidity: 0 to 95% non-condensing.
Electrical and network
A. Supply: 12Vdc from the iCANnet network.
B. Counts as 1 device load when used with 4
LED outputs or with 1 sensor.
C. Every additional 2 sensors increases the
supply load by 1 device.
D. Will operate from 12Vdc to 18Vdc.
E. iCANnet network connection: 2 part
connector with screw terminals. Wire sizes
from 4mm2 (12AWG) – 0.25mm2 (24AWG).
F. Maximum wiring distance of inputs should
not exceed 10m (32 feet).
Installation
Supplied Parts
The universal interface is supplied with a
mounting plate for easy attachment to a
standard double gang UK style electrical back
box (not included).
Mounting
The mounting plate can be removed if it is
not required, allowing the universal interface
to be mounted in any convenient location. If
doing so, you must ensure that the universal
interface is supported such that it is electrically
isolated from any electrically conductive
material in that location. The unit must be
installed in a dry,
ventilated location where ambient temperature
and humidity are within the operating limits of
the product.