Eaton - Lighting Systems iLight Product Series - UIG-2 73-898-00 IM8840 Iss.02 7
Operation
The UIG-2 provides the standard input
functions which are available from the
iCANsoft application. For details
about the general use of iCANsoft, please refer
to the system Manual.
In addition, the UIG-2 provides sequences and
partitioning/ room join functions.
Sequences
Sequences allow a number of individual
actions (steps) to be linked together in order to
cause multiple operations from a single trigger
action.
The UIG-2 provides up to 16 sequences with
up to 128 steps each, with or without time
delays between steps.
The iCANsoft System Manual gives more
details on programming sequences.
Partitioning/Room Join
The UIG-2 allows for the programming of
simple room join functions, by using partitions.
The room join function operates by linking
areas.
A physical room partition can be detected by a
switch on the UIG-2 inputs. When the partition
is opened, an action in one of the areas will
cause the equivalent action in the other area.
The UIG-2 allows 4 room joins with up to 3
partitions each.
A Technical Note on Room Joins and
partitioning, with examples, is available.
LED Output Drives
The unit has four LED drive outputs, each rated
at 6.7V 10mA, which can be used to give visual
indication of programmed functions.
The outputs will indicate input selection for
the optoisolated digital inputs when they are
configured for scene selection.
The LED outputs can also be configured from
iCANsoft for indication of other functions.
LEDs are connected between the appropriate
output and the 0V connection. Wire distance
from the device to the UIG-2 should not
exceed 10m (32 feet).