30
Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual 164000639—Rev 03
2.
If not already removed, remove the front cover by loosening the left and right side bottom mounting bolts
and remove the two mounting bolts on the top. Lift the cover to disengage the cover from the bottom
bolts then set the cover to the side in a safe location. Retain the hardware for later use.
3.
Remove the screws securing the internal safety shield panel and remove the panel to gain access to the
battery power terminals. Retain the hardware for later use.
NOTE 1
Line-up-and-match positive and negative battery wiring is factory supplied coiled inside
the IBC–SW.
NOTE 2
Ferrules are installed on the ends of the factory supplied wiring. Do not shorten or cut
factory supplied wiring.
4.
Route the battery wiring (positive and negative) from the UPS DC Input terminals through the bottom side
inter-cabinet access pass-through (see
) of the UPS cabinet and IBC–SW to the wiring channel on
the left side of the IBC–SW (see
). Route the wiring along the wiring channel to the IBC–SW DC
Output terminal block. See
for terminal locations. See paragraph
IBC–SW Power Wiring Preparation
and
for wiring requirements. Refer to the applicable Eaton
93PM UPS Installation and Operation manual listed in paragraph
, for UPS cabinet
terminal locations.
5.
Secure the battery wiring to the wire tie anchors (see
) using Zip ties.
6.
Route the battery cabinet ground wiring from the UPS through the bottom side inter-cabinet access pass-
through (see
Line-Up-and-Match Power Wiring
) of the UPS cabinet and IBC–SW to the IBC–SW
ground terminal block. See
for terminal location. See paragraph
IBC–SW Power Wiring Preparation
and
for wiring requirements.
WARNING
Verify polarity of connections. Risk of personal injury and damage to equipment from arc flash if connections
are reversed.
7.
Connect the positive and negative power wiring to the IBC–SW DC (
+
) and IBC–SW DC (
–
) output
terminals. Connect the ground wiring to the IBC–SW ground terminal. See
for termination
requirements.
For a detailed view of the IBC–SW terminal block, see
.
8.
Connect the positive, negative, and ground power wiring from the IBC–SW to the UPS cabinet external
battery input and ground terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation
manual listed in paragraph
, for UPS cabinet termination requirements.
NOTE
Route the battery wiring between the UPS and subsequent IBC–SWs through the
bottom of the adjacent IBC–SW.
9.
If installing more than one IBC–SW, repeat
Steps 2
through
8
for each IBC–SW, and then proceed to
paragraph
Installing IBC–SW Interface Wiring
; otherwise, proceed to paragraph
Installing IBC–SW Interface Wiring
.
NOTE
The internal battery string is to be connected by an authorized Eaton Customer Service
Engineer at system startup.