background image

Before You Begin 

i-on30EX/EXD 

Page 12 

Power Availability 

Before connecting any external devices to the 
control unit, you must make sure that the control 
unit can provide sufficient current to power the 
system during a mains failure for the time required 
to meet the appropriate standard.  

EN51031-1 Grade 2 and PD6662 Grade 2 both 
require 12 hours standby time. 

Note: When calculating the average load during 
the standby time period you must allow for at least 
two periods in alarm. To take the worst case these 
two periods of alarm should each be 15 minutes 
long, the maximum permitted in EN50131-1 
section 8.6. 

The amount of current available from the control 
unit depends on the size of battery fitted and its 
health. The current taken by the control unit PCB, 
communicator and keypads is given in 

Technical 

Specifications 

– EN50131-6 Ratings

 on page 35. 

The following calculation shows a simplified 
example: in an alarm system with an i-
on30EX/EXD control unit, two i-kp01 keypads, 
and 15 wired PIRs the system takes the following 
total quiescent current: 

Device

 

Current

 

Control unit PCB 

100mA 

15 x PIRs at 15mA each 

225mA 

1 x (wired expander) 

20mA 

2 x i-kp01 at 30mA each 
(backlights off) 

60mA 

Siren (quiescent) 

25mA 

Total 

430mA 

During an alarm, these figures become: 

Device

 

Current

 

Control unit PCB 

120mA 

15 x PIRs at 15mA each 

225mA 

1 x (wired expander) 

20mA 

2 x i-kp01 at 60mA each 
(backlights off) 

120mA 

Siren (in alarm) 

400mA 

Total 

885mA 

The total amp hours required =  

(0.430 A x 11.5h) + (0.885A x 0.5h) = 5.39Ah 

One new, fully charged, 7Ah battery can provide 
the charge required by the example system and 
would meet the Grade 2 requirements. 

Note: All current drawn from the Aux terminals 
(12V) must be included in the overall calculation. 

CAUTION: Ensure that the system does not 
demand more than the maximum current available 
from the control unit during an alarm, see page 
35. 

Bus Cabling Requirements 

Cable Type 

In general, the control unit requires standard 7/0.2 
un-screened four core alarm cable for wiring the 
bus. 

For maximum performance in harsh environments 
use twisted pair screened cable with a 
characteristic impedance of 100-120ohms eg: 
Belden 8132 or cable designed for RS485. 

Use one pair for data lines A and B. Use the other 
pair for 12V and 0V. For optimum performance 
the voltage at the keypads and expanders should 
be greater than 12V.  

Screened cable may prove necessary if the 
installation site has equipment that produces high 
levels of R.F. (Radio Frequencies). For example, 
welding equipment is known to produce a large 
amount of radio interference. If screened cable is 
required, you should keep to the following 
guidelines: 

1.  Avoid earth loops by connecting the screen on 

the cable to mains earth at the control unit but 
not at the keypad or expander. 

2.  The continuity of the cable screen is most 

important and screens MUST be continuous 
along the full length of the cable. 

3.  Where the cable enters any metal enclosure, 

ensure the screen is isolated from the case. 

Cable Segregation 

Segregate the bus cabling from any other wiring, 
such as mains supply cables, telephone cables, 
computer network cables and R.F. cables. Use 
cable ties to keep cables separated. 

Keep the bus cable clear of cables supplying 
sounders, extension loudspeakers or any other 
high current devices. 

Cable Configuration and Length 

You can connect up to 10 devices to the control 
unit bus. You may connect the devices either in 
daisy chain (serially), or in star (parallel) 
configuration at the control unit connector. 

Summary of Contents for i-on30EX

Page 1: ...i on30EX i on30EXD Security System Installation Guide Issue 6...

Page 2: ...erting you to potential problems or hazards Each of these are marked by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not...

Page 3: ...re Closed Circuit Connections 20 Fully Supervised Loop Connections 20 Step 7 Connect Wired Outputs 22 Control Unit Wired Outputs 22 Wired External Sounders Optional 22 Wired Outputs on Expanders 22 Wi...

Page 4: ...i on30EX EXD Page iv This page is intentionally blank...

Page 5: ...grammable output and an external prox reader KEY EP A range of wireless peripherals is available for operation with the wireless expanders The range includes a door contact universal transmitter a pas...

Page 6: ...cable The Installer Menu allows you to specify all the operating parameters for an individual installation If you wish you can also connect a PC or laptop to the mini USB port on the control unit PCB...

Page 7: ...ll affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for more infor...

Page 8: ...poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the i on30EX its expanders and keypads have been tested for Electromagnetic Compatibility EMC However when handling...

Page 9: ...t 1 Connectors for system bus 2 Zone output and Aux power connectors 3 Plug by output connectors 4 Tamper switch 5 ADSL filter pins i on30EXD only 6 On board communicator connections i on30EXD only 7...

Page 10: ...XD Page 6 1 Built in communicator telephone line connector i on30EXD only 2 Siren and strobe 3 Loudspeaker 4 Bus cable connector 5 Output transistorised 6 Aux power 7 Wired zone connectors Figure 3 Co...

Page 11: ...To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing...

Page 12: ...to gently push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 8 Gently swing the lower side of the front out from...

Page 13: ...inals for zones 4 Sounder volume control 5 Connector for data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing not used in i onEX control units 6b LED functions and RS48...

Page 14: ...aker connectors 19 Outputs Figure 14 EXP W10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper s...

Page 15: ...sable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Loud...

Page 16: ...ent drawn from the Aux terminals 12V must be included in the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an...

Page 17: ...a star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 17 If required fit the termination jumper at the devices o...

Page 18: ...360mA 0 58V 1 15V 1 73V 2 30V 2 88V 3 46V 4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Re...

Page 19: ...and location for the user Out of sight of potential intruders Do NOT site the keypad s Next to electronic equipment particularly computers photocopiers or other radio equipment CAT 5 data lines or ind...

Page 20: ...s You can set the function of the backlights in either of two ways a Use the Installer Menu Detectors Devices Wired Keypads Edit Keypad Keypad n Backlight option See the Engineering Guide for more det...

Page 21: ...on key will glow for 20 seconds after the last press this may be useful when the keypad is placed in bedrooms that should be completely dark at night MENU STATUS OK LED 4 Leave local programming mode...

Page 22: ...fixing plate and then slide it a short distance parallel to the body of the prox reader 3 Slide the fixing plate away from the reader body along the cable Figure 23 Opening External Prox Reader Figure...

Page 23: ...peakers During normal operation loudspeakers on expanders repeat setting and entry tones for the partition that the expander is allocated to During an alarm the loudspeakers repeat alarm tones Each lo...

Page 24: ...ne Wiring Two Wire Closed Circuit Connections With version 4 02 and higher software you can connect two wire CCL detectors to each pair of zone terminals To specify the zone wiring type use the Instal...

Page 25: ...on a KEY KPZ01 Note that the resistance values shows are examples Figure 35 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resistor values for the control unit in Installer Menu System...

Page 26: ...minal on the control unit see item 10 in Figure 3 as either CC or FSL Use Installer Menu System Options Panel Tamper Rtn By default the terminal is CC If you program the TR terminal as FSL then make s...

Page 27: ...any other FSL resistor combinations CC wiring Eaton s Security Business does NOT recommend that you use CC wiring for this application The maximum length of wire allowable is only 6m Instead Eaton s...

Page 28: ...PABX exchanges with or without secondary proceed indication Note The built in communicator is not suitable for connection as an extension to a pay phone or to 1 1 carrier systems Approval The built i...

Page 29: ...nal Installer after 14 days written notice to the authorised maintainer To connect the telephone line see Figure 45 i Using a two core telephone cable strip off 5mm and feed the cable through one of t...

Page 30: ...hen the fault is absent Tell Back Input This input is designed to allow a plug by communicator to indicate to the control unit that the user can reset the system after a system tamper The communicator...

Page 31: ...rt pause the keypad gives a confirmation tone The display briefly shows the bus address of the keypad If there are no other keypads connected to the bus it should be b1 d51 bus 1 device 51 Keypads tak...

Page 32: ...flashes a second Each of these sequences has the following meaning No Flashes Meaning One Communication with control unit over bus is OK Two No communication over the bus in the last 10 seconds Three...

Page 33: ...trying to set the system from a keypad will see the message Installer on Site All HUAs including radio HUAs fire alarm zones 24 hour zones and tampers are disabled If you have logged into the system...

Page 34: ...ctory default options without defaulting the user and installer access codes then 1 From the Installer Menu select System Options Restore Defaults Factory Defaults The display shows 2 EITHER Press to...

Page 35: ...ed description Note make sure that you allocate keypads correctly to partitions For more information see Assigning Wired Keypads to Partitions in the i on Range Engineering Guide Assemble and close th...

Page 36: ...er Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation UK Confirmation Mode Basic...

Page 37: ...is disabled 18 Appears only if Report Mode Fast Format AND Confirmation Mode Basic 19 Shows None on i on30EXD 20 Must be activated by a Eaton s Security Business External Support Manager 21 Appears o...

Page 38: ...r you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its sounder Once you have found the bus device you ca...

Page 39: ...y available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains supply frequency User Codes 50 plus installer code Remote controls 50 one...

Page 40: ...h sealed lead acid not supplied Low battery fault at 12V Aux power output fault at 9V Deep discharge protection at 10 0 5V Serviceable components Mains fuse 250mA T Standby time See Power Availability...

Page 41: ...3rEUR 00 Pet tolerant PIR 714rEUR 00 PIR Transmitter Small case 720rEUR 00 Smoke Detector Transmitter 734rEUR 00 01 CC FSL Door Contact Transmitter white 734rEUR 05 06 CC FSL Door Contact Transmitter...

Page 42: ...i on30EX EXD Page 38 NOTES...

Page 43: ...i on30EX EXD Page 39 NOTES...

Page 44: ...EXD Page 40 Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number 12435139 21 1...

Reviews: