background image

IM0217.Revision 5     05/17                                                        

Page 3 of 3

Fig.3 Wiring diagram(Normal version

Fig.4 Wiring diagram(Emergency version)

10. Maintenance/Servicing

10.1 General

The relevant national regulations which apply to the 
maintenance/servicing of electrical apparatus in 
explosive atmospheres, shall be observed (IEC/EN 
60079-17). The interval between maintenance 
depends upon the ambient conditions and the hours 
of operation. The recommendations given within IEC 
60079-17 for recurring checks must be observed. 

10.2 Checks

The equipment must be de-energised before opening 

Visual inspection should be carried out at a minimum 
of 12 monthly intervals and more frequently if 
conditions are severe, refer to IEC/EN 60079-17. The 
time between lamp changes could be very infrequent 
and this is too long a period without inspection. 

10.3 Routine Examination

During maintenance, the parts affecting the level of 
protection must be checked in particular:
- Ensure the lamp is lit when energised and examine 
the enclosure and glass for any signs of cracks and 
damage.
- When de-energised and left to cool, there should be 
no significant sign of internal moisture. If there are 
signs of water ingress, the luminaire should be opened 
up, dried out, and any likely ingress points eliminated 
by re-gasketing, re-greasing or other replacement.
- Check the gasket of terminal chamber gasket and LED 
housing for any damage or permanent set and replace 
as required.
- To maintain the light output, clean the protective 
glass periodically with a damp cloth or a mild cleaning 
fluid.
- If this product is used in the combustible dust area, 
outside of enclosure must be cleaned on a regular 
basis to prevent accumulation of dust.
- Terminal, screw glands and blanking plugs for secure 
fitting.
- The terminal chamber should be opened periodically 
and checked for moisture and dirt ingress. The cable 
connections should be checked for tightness. The 
gasket should be checked for cracks or lack of 
elasticity, and if necessary, replaced. Cover bolt 
torque: 1.5~2Nm.
- The flameproof path can not be readily checked, it 
will not go out of shape. 
- The battery should be charged and discharged once 
every 6 months.
- Check that mountings are secure and the adjusting 
bolts are tight.
- If it has been suspected that the luminaire has 
mechanical damage, a stringent workshop overhaul 
will be required. Where spares are needed, these must 
be replaced with factory specified parts. 
No modifications should be made without the 
knowledge and approval of the manufacturer.

Cleaning the rests of grease and corrosion do not use 
sharp metallic devices that can damage the threads of 
the joint, and greasing them using appropriate grease 
terminally and  chemically stable with a drop 
point≥200

like e.g.: HTL lubricant from Cooper 

Crouse-Hinds! When the housing need to be repainted, 
pay attention that the flameproof joints test without 
any part with coating!

11. Repair/Overhaul/Modifications

11.1 General

The national regulations EN/IEC60079-19 have to be 
observed! Repairs and overhaul may only be carried 
out with genuine Cooper Crouse-Hinds spare parts.

Before replacing or disassembling individual parts, 
observe the following:

Disconnect the power supply to the equipment before 
maintenance/repair. 
Make sure that there is no explosive atmosphere 
when opening the equipment. 

See section 8.4 for 

notes on opening and closing the lamp. 

Battery pack replacement: 

In the case of battery failure, the battery pack must be 
replaced as a complete unit from the manufacturer. 
First, open the cover, then change the failure battery, 
last, close the cover.

Only use original spare parts. If the luminaire was 
previously in operation then wait to cool enough 
before opening. Repairs that affect the explosion 
protection, may only be carried out by Cooper
Crouse-Hinds or a qualified electrician in compliance 
with the applicable national rules. Modifications to 
the device or changes to its design are not permitted.
After carrying out repair or overhaul work, ensure 
that the “Exde" properties have not been affected.
Assistance may also be obtained through Cooper 
Electronic Technologies (Shanghai) Co., Ltd. Sales 
Service department, 
955 ShengLi Road, Pudong Shanghai 201201
Phone (86) 21-28993943

12. Disposal/Recycling

When the apparatus is disposed of, the respective 
national regulations on waste disposal will have to be 
observed.

The charging conductor L1 and the luminaire’s 
mains connection must always be connected 
to the same external conductor of the mains 
supply! 
See Fig.2, Fig.3 Fig.4 and Fig.5 for details.

9. Putting into operation

Prior to putting the apparatus into operation, 
the tests specified in the relevant national 
regulations shall be carried out. Insulation 
measurements may only be carried out 
between PE and the external conductor L1 (L2, 
L3) as well as between PE and N.
- Measurement voltage: Max. 1 KV AC/DC
- Measurement current: Max.10 mA
- The luminaire may only be operated when 
closed.
- It is generally recommended (see IEC/EN 
60079-14) that you ensure the type of 
protection of the construction is not impaired 
during installation.

(1). HPL — Indicates basic catalog series designation.

(2). Indicates Total Luminous Flux.

-3L—3000Lm, -4L—4000Lm, -5L—5000Lm

-6L

6000Lm, -7L

7000Lm, -8L

8000Lm

(3). Indicates LED colour temperature.

Default — 5700K, -W — 3000K

(4). Indicates Optics type.

Default — Type V optic standard

(5). Indicates ballast voltage.

Default — 100-240V AC 50/60Hz, 108-250V DC 

(6). Indicates entry type and size.

-1M — M20

×

1.5, -2M — M25

×

1.5

-D1 — M25

×

1.5(only use for Direct entry)

(7). Indicates Entry quantity.

Default — One entry, -S886 — Dual entry

(8). Indicates Terminal:

-T1—Pillar terminal, -T2—MK 6/3, -T3— MK 6/6,

-T4—MUT 4

3 pole

, -T5—MUT 4

6 pole

(9). Indicates Glass

Default—Clear Glass, -F—Foggy Glass

(10). Indicates Entry Acc.

Default—No entry acc, -1P—two entries with 1 Plug

-2G—all entries, with plastic cable gland

-3G—two entries, with 1 plastic plug, 1 cable gland

(11). Indicates Mounting Type. 

Default—G3/4 Pendant mount only

-B1—With Painted bracket mount only

-B2—with 304SST bracket mount only

-B3—with 316SST bracket mount only

-B4—with both Painted bracket mount, 

also available for G3/4 Pendant mount

-B5—with both 304SST bracket mount, 

also available for G3/4 Pendant mount

-B6—with both 316SST bracket mount, 

also available for G3/4 Pendant mount

-B7—G3/4 Pendant mount, also with mounting

bracket hole cut, but bracket need to order separated.

-B8—only with mounting bracket hole cut, 

mounting bracket need to be ordered separated.

(12). Emergency duration

Default—Normal version

EM1—1.5H, 30% output; EM2—3H, 15% output;

13.

Catalog No. definition

HPL -3L -W

-1M -S886 *

*

*

*

*

(1) (2) (3) (4) (5) (6)

(7)

(8) (9) (10) (11) (12)

Fig.5 Wiring diagram

For version with cable
Brown: L
Blue: N
Black: L1
Yellow/Green: Ground

For version with cable
Brown: L
Blue: N
Yellow/Green: Ground