4. Conformity with standards
This explosion protection floodlight meet the requirements of IEC/EN 60079-0,
IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-18, IEC/EN 60079-31. It also complies
with the EC Directives for “Apparatus and protective system for use in explosion
atmospheres” (2014/34/EU). It has been designed, manufactured and tested in
accordance to the state of the art and according to ISO 9001:2000. The luminaires
are suitable for use in explosive atmospheres, Zone1,Zone2 according to IEC60079-
10-1 and dust area Zone21 and Zone22 according to IEC60079-10-2.
5. Fields of Application
The ATEX category 2 GD Luminaire with a separate Exe terminal box utilizes Ex dem
protection and IP66 sealing making it suitable for use for potentially explosive
atmospheres including ignitable gas and dust applications.
The luminaire is designed for use in Zone1/Zone21 and Zone2/Zone22 hazardous
areas in indoors and outdoors in Marine and Wet locations, where moisture, dirt,
corrosion, vibration and rough usage may be present. Application ambient
temperature is -40ºC~+40/45/50ºC for different version. Refer to the luminaire
nameplate, For specific information, corresponding operating temperature(T-Code).
The enclosure materials used, including any external metal parts, are High quality
materials that ensure a corrosion resistance and resistance to chemical substances
according to the requirements for use in a “normal“ industrial atmosphere. In case
of use in an extremely aggressive atmospheres, please refer to manufacture.
3. Safety Instructions
This product should be installed, inspected, and maintained by a qualified
electrician only, in accordance with national regulation, including the relevant
standard and, where applicable, in acc. With IEC/EN 60079-17 on electrical
apparatus for explosive atmospheres. The national safety rules and regulations
for prevention of accidents and the following safety instructions in these
operating instructions, will have to be observed!
The luminaire must not be operated in Zone0 and in Zone20!
When using in Zone21,Zone22, the requirements of IEC/EN 60079-14 relating to
temperature must be observed. The indicated surface temperatures in table 7
are not related to a layers above 5 mm thickness.
Do not install where the marked operating temperature exceed the ignition
temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
luminaire nameplate.
The luminaires shall be operated as intended and only in undamaged and
perfect conditions! And Keep tightly closed when in operation!
The technical data indicated on the luminaire are to be observed!
Change of the design and modifications to the luminaire are not permitted!
Multiple, short-term switching must be observed!
Only genuine Cooper Crouse-Hinds spare parts may be used for replacement!
Repairs that affect the explosion protection, may only be carried out by
Cooper Crouse-Hinds or qualified electrician!
!
1.
Dimensions
Normal version/Indirect entry
EM version/Indirect entry
EM version
Direct entry
2. Technical data
Hazardous area specification
Type of protection: Ex d e m & Dust protected enclosure
ATEX classification: Group II Category 2 G D
Certification Marking:
II2 G Ex db e mb op is IIC T6 Gb
II2 D Ex tb IIIC T80ºC Db IP66
Ambient temperature: -40ºC~+40ºC/45 ºC/50ºC
Temperature class: Refer to Type configuration
EC type examination
Certification No.: EPT 16ATEX 2405
IECEx Certificate No.: IECEx CQM 15.0054X
Degree of protection: IP 66 acc. to EN60529/IEC60529
Approval of the production
Quality assurance: Baseefa ATEX 5952
Enclosure specification
Material of enclosure: Aluminum alloy without Cu
Finish: Painted polyester power coating
Material of globe: Tempered glass
Mounting bracket: Stainless steel or Steel painted
Fasteners: All external fasteners stainless steel
Installation: Mounting bracket with aiming quadrant
Weight: Refer to Type Configuration.
Entry specification
Indirect entry
: M20
×
1.5 or M25
×
1.5 cable entry. One entry is fitted
with an Exe stopping plug.
Direct entry
: Exd M25
×
1.5 cable entry.
Electrical specification
Wattage: 25W~80W
Voltage: AC: 100V-240V 50/60Hz, DC: 108~250V
Lamp: LED Arrays
CRI: 70
Insulation class: I acc. to IEC60598
Terminals capacity: 3 core or 6 core conductor/cable
Solid: 0.5~6mm
2
, Flexible: 0.25~4mm
2
6. Cable gland recommend
Entry size
Part No.
Cable size
Torque (Nm)
screw-in enclosure For cable
M20
CAP816609
8.5-16
20
20
M25
CAP816709
12-21
30
30
M25
CCL0803086
12-15
25
42
Note: Mounting the selected cable glands acc. type and dimensions of
the main connection cable. Following their manufacturer instructions.
Normal version
Direct entry