5
The Overview screen (only available with multi-view firmware HMI) shows the current
status of up to 8 ATS-900 controllers. In the example above, Station 1 is
communicating and shows power connected through S1. Station 2 has timed out and
is trying to reconnect automatically. Station 4 is connected to S2 (preferred source).
Stations 5, 6, and 7 all have various alarm conditions which are displayed by the status
window below each station. Station 8 is disabled per the user.
To view more details and controls for any communicating controller, press anywhere
inside the summary window of the desired controller. This will take you to the
Controller View screen (section 4.2) for that particular controller.
To enable/disable controllers, press on any disabled station window and enter your
password. See section 4.4 for more information on the System Setup screen.
If any controller has an Alarm
condition, an audible alarm will
sound from the HMI. To view the
alarm, press on the alarmed
controller window. Once you are
on the Controller View screen, an
alarm popup window should be
displayed. To silence the alarm,
press “Silence Alarms” button.
To perform a remote alarm reset,
press the “Remote Alarm Reset”
button. To close the alarm
popup, simply press “Close”.