background image

6

Instruction Leaflet 

IL 29C702E

Effective April 2015

Installation Instructions for the HKDDC 

Circuit Breaker and Molded Case Switch

EATON CORPORATION www.eaton.com

3. Inspection and Field Testing

Series C molded case circuit breakers are designed to provide years 

of almost maintenance-free operation. The following procedure 

describes how to inspect and test a circuit breaker in service.

Inspection

Circuit breakers in service should be inspected periodically. The 

inspection should include the following checks 3-1 through 3-8.

 WARNING

BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, 

MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF POSITION 

AND THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE 

PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED 

APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. THE VOLTAGES 

IN ENERGIZED EQUIPMENT CAN CAUSE SEVERE PERSONAL INJURY OR 

DEATH.

 CAUTION

MAKE SURE THAT CLEANING AGENTS OR SOLVENTS USED TO CLEAN 

THE CIRCUIT BREAKER ARE SUITABLE FOR THE JOB. SOME COMMERCIAL 

CLEANING AGENTS WILL DAMAGE THE NAMEPLATES OR MOLDED 

PARTS.

3-1. Remove dust, dirt, soot, grease, or moisture from the surface 

of the circuit breaker using a lint-free dry cloth, brush, or vacuum 

cleaner. Do not blow debris into circuit breaker. If contamination is 

found, look for the source and eliminate the problem.
3-2. Switch circuit breaker to ON and OFF several times to be sure 

that the mechanical linkages are free and do not bind. If mechanical 

linkages are not free, replace circuit breaker.
3-3. With the circuit breaker in the ON position, press the PUSH 

TO-TRIP button to mechanically trip the circuit breaker. Trip, reset, 

and switch circuit breaker ON several times. If mechanism does 

not reset each time the circuit breaker is tripped, replace the circuit 

breaker.
3-4. Check base, cover, and operating handle for cracks, chipping, 

and discoloration. Circuit breakers should be replaced if cracks or 

severe discoloration is found.
3-5. Check terminals and connectors for looseness or signs of over-

heating. Overheating will show as discoloration, melting, or blister-

ing of conductor insulation, or as pitting or melting of conductor 

surfaces due to arcing.
If there is no evidence of overheating or looseness, do not disturb or 

tighten the connections. If there is evidence of overheating, termina-

tions should be cleaned or replaced. Before re-energizing the circuit 

breaker, all terminations and cable should be refurbished to the con-

dition when originally installed.
3-6. Check circuit breaker mounting hardware, and tighten if neces-

sary.
3-7. Check area where circuit breaker is installed for any safety haz-

ards, including personal safety and fire hazards. Exposure to certain 

types of chemicals can cause deterioration of electrical connections.

Field Testing

Any field testing should be done in accordance with applicable 

NEMA Standards.

Figure 12. Circuit Breaker Manual Controls.

Summary of Contents for HKDDC Series

Page 1: ...s e D Introduction 2 Installation 3 Inspection and FieldTesting 6 Effective April 2015 Supersedes IL 29C702D Dated 01 11 Instruction Leaflet IL 29C702E Installation Instructions for the HKDDC Circuit...

Page 2: ...tions Figure 1 Type HKDDC Series C DC Circuit Breaker FrameWith KT Trip Unit Installed 1 Introduction General Information In this document the term circuit breaker includes molded case switches The K...

Page 3: ...tended installation by comparing nameplate data with existing equipment ratings and system requirements lnspect the circuit breaker for completeness and check for damage before mounting Uninstalled co...

Page 4: ...Terminal Installation WARNING BEFORE MOUNTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED SPECIAL ATTENTION SHOULD BE PAID TO REVERS...

Page 5: ...t Drilling Figure 11 Circuit Breaker Escutcheon Dimensions for 3 Pole Circuit Breakers 2 7 Connect line and load conductors and accessory leads 2 8 If required install terminal shield on circuit break...

Page 6: ...ch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind If mechanical linkages are not free replace circuit breaker 3 3 With the circuit breaker...

Page 7: ...7 Instruction Leaflet IL 29C702E Effective April 2015 Installation Instructions for the HKDDC Circuit Breaker and Molded Case Switch EATON CORPORATION www eaton com Notes...

Page 8: ...ormation purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representative The sale of the product shown in this litera...

Reviews: