Warnings
• DC leakage protection is provided by means of electrical galvanic
separation and an internal Insulation Monitor Device (IMD).
• Eaton recommends that DC EV chargers installed in a TT system
are equipped with an RCD upstream according to IEC 60364-7-722.
• Eaton recommends that DC EV chargers installed in a TN system
where a fire hazard is present are equipped with an RCD upstream
in accordance with IEC 60364-7-722.
• Eaton’s support team can help with the selection of the proper RCD
to be used.
• In case of connection in TN-C-S networks, earth rods must be used.
• It is not possible to install the unit in an IT grid configuration.
• Always refer to local regulations which may differ from and can
supersede the international regulations listed above.