Explosion-protected safety switch 10A,  
GHG 261

Field of application

The safety switches GHG 261 are intended for 
use in potentially explosive atmospheres in 
Zones 1 and 2 as well as in Zones 21 and 22 in 
accordance with IEC/EN 60079-10-1 and  
IEC/EN 60079-10-2. 

The enclosure materials used, including any 
external metal parts, are high quality materials 
that ensure a corrosion resistance and 
resistance to chemical substances according to 
the requirements for use in a ”normal industrial 
atmosphere”:

– impact resistant polyamide 
– special steel AISI 316 L.

For use in an extremely aggressive atmos-
phere, please contact  your Cooper Crouse-
Hinds agent for additional information on the 
chemical stability of the plastics used.

 5  Application / Properties

The safety switches are designed for the safe 
isolation of the electrical energy at all poles 
while maintenance, cleaning and repair work is 
being carried out on equipment, machinery and 
drives in potentially explosive atmospheres. 
See technical data, page 6, for the temperature 
class, explosion group and permissible ambient 
temperature.

Due to the AC 3 motor switching capacity  
of the safety switches, reliable isolation 
(switching) is also possible during operation.

In addition to this, the safety switches are so 
designed, that they also switch off the drive, 
e.g. via the contactor that precedes the 
auxiliary contact. In relation to the main 
contacts, this auxiliary contact is lagging while 
making and leading while breaking.

Versions with gold-tipped auxiliary contacts are 
suited for switching extra-low voltage circuits.  
Special attention shall be paid to the maximum 
current load (see technical data, page 6). The 
contact chamber of the gold-tipped version is 
marked with the letter ”G” or colour-coded.

Due to the mechanical design of the safety 
switch, compulsory opening of the contacts is 
possible.

The safety switches fulfil the isolating 
properties according to IEC/EN 60947-3.

The ”EMERGENCY-STOP“ version conforms to 
the requirements of IEC/EN 60204-1.

To prevent unauthorized switching, the 
switches can be locked in the ”OFF“ position 
by means of 3 padlocks, see fig. 1, (shackle 
diameter of the padlocks up to 4 to 6 mm).

A built-in locking device prevents the opening 
of the enclosure in the ”OFF“ position.

The data according to sections 3 and 4 shall 
be taken into account during use.

Applications other than those described are 
not permissible without a written declara-
tion of consent from Messrs. COOPER 
Crouse-Hinds.

During operation the instructions stated in 
section 7 of the operating instructions shall 
be observed.

The sole responsibility with respect to the 
suitability and proper use of the control 
switches with regard to the basic require-
ments of these instructions (see technical 
data) lies with the operator.

6 Installation

The relevant national regulations(e.g. Elex V, the 
equipment safety law for Germany) and the 
generally recognized rules of engineering apply 
for the installation and operation 
(IEC/EN 60079-14).

The improper installation and operation of 
safety switches may result in the invalida-
tion of the guarantee.

6.1 Mounting

Before mounting the safety switch, the cover 
has to be removed from the enclosure base. 
For this, the switch has to be set to the ”ON“ 
position.

When the safety switches are mounted directly 
onto the wall,  they shall rest evenly only on the 
fastening points provided for this purpose.

The screw chosen shall fit the fixing hole (see 
dimensional drawings, page 6) and shall not 
damage the hole (e.g. use of a washer).

The apparatus shall be fixed diagonally with a 
minimum of 2 screws.

If the screws are overtightened, the 
apparatus may be damaged.

The safety switches GHG 261 are suited for 
mounting on CEAG apparatus holders size 1 by 
means of self-cutting screws (see fig. 2). 

See the respective mounting instructions.

6.2  Opening apparatus /  
 

Electrical connection

The electrical connection of the apparatus 
may only be carried out by specialists 
(IEC/EN 60079-14). 
Before opening the apparatus, ensure that it 
has been  isolated from the voltage supply 
or to take suitable protective measures.

Before opening, set the switch to the ”ON“ 
position.

   

C

   

C

 Fig. 1

Apparatus holder size 1 

for wall and trellis fixing

Apparatus holder size 1  for pipe fixing

C = screw fixing points for safety switch

GHG 261, 10A

 Fig. 2

Wiring diagram

 Fig. 3