Step 6

Center the splice body over the compression connector, 

using the raised areas on the cable entrances of the splice 

body as indicators. (See Figure 6.) Run one of the neutral 

wires from cable #2 through the drain wire tabs on both 

ends of splice as shown. Ensure neutral wires are twisted 

tightly to grounding tab. Terminate this neutral wire in the 

concentric neutral compression connector.
Bundle both sets of concentric wires into a single conductor 

and jumper across the splice body.
Using the appropriate compression connector (user 

supplied), connect the concentric neutrals together.

Step 7

Slide the rejacketing sleeve into place so that it covers the 

entire area that was exposed when the cable jacket was 

originally removed. Install the rejacketing sleeve per the 

manufacturer's recommended instructions.

Figure 6. Cutaway of installed splice.

CONCENTRIC NEUTRAL 

CONNECTED TOGETHER

SINGLE CONCENTRIC NEUTRAL 

(BOTH ENDS)

CENTER SPLICE BETWEEN BUMPS

Table 2. Typical Crimping Tools

Connector

Size

Connector

O. D.

(Inches)

Mfg.

Tool

Die

#3 Str. 

Thru 

3/0 Sol.

0.640
(16 mm)

Burndy

MD-6

Y35

W-BG

U-BG

Kearney

O

5/8"

620

H1    H2

H3

9/16"

T & B  

EEI Equiv.

OD58

5/8"

8A

3/0 Str.  

Thru  

250 Comp.

0.775  

(20 mm)

Burndy

MD-6

Y35

W247

U27ART

Y 35  Y39

Y45   Y47

U247

U27ART

Kearney

O

737

747

H1   H2

H3

737

747

T&B

TBM-15

66R

Alcoa

12A

839EA

EEI Equiv.

10A

Table 1.  Measurement Guide

0.775"

(20 mm)

0.640"

(16 mm)

0.775" DIA.

(20 mm)

SHOWN

1

/

8

"

(54 mm)

Compression Connector

O.D. Measurement Guide

Compression Connector

Length Guide

ote:

N

Install as many crimps as possible without 

overlapping. Rotate each successive crimp 90° to 

prevent distortion.

4

15 KV AND 25 KV CLASS EZ II SPLICE INSTALLATION INSTRUCTIONS

   MN650007EN   January 2016   

Summary of Contents for EZ II Series

Page 1: ...15 kV and 25 kV class EZ II splice installation instructions For A B and C cable ranges only COOPER POWER SERIES Splices MN650007EN Effective January 2016 Supersedes April 2015...

Page 2: ...FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF T...

Page 3: ...Contents SAFETY INFORMATION Safety Information iv PRODUCT INFORMATION Introduction 1 Acceptance and Initial Inspection 1 Handling and Storage 1 Standards 1 Description 1 PREPARATION OF CABLES TO BE S...

Page 4: ...king around high voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal inju...

Page 5: ...on receipt inspect the shipping container for signs of damage Unpack the splice and inspect it thoroughly for damage incurred during shipment If damage is discovered file a claim with the carrier imme...

Page 6: ...1 1 8 29 mm of the cable insulation exposing the bare conductor Remove sharp edge of insulation by beveling at 45 angle for approximately 1 8 3 mm See Figure 3 Clean the cable insulation with an appr...

Page 7: ...rds the end of the connector Rotate each crimp 90 Install as many crimps as possible without overlapping crimps Note N After crimping remove any sharp edges or raised points on the compression connect...

Page 8: ...rejacketing sleeve per the manufacturer s recommended instructions Figure 6 Cutaway of installed splice CONCENTRIC NEUTRAL CONNECTED TOGETHER SINGLE CONCENTRIC NEUTRAL BOTH ENDS CENTER SPLICE BETWEEN...

Page 9: ...This page is intentionally left blank 5 15 KV AND 25 KV CLASS EZ II SPLICE INSTALLATION INSTRUCTIONS MN650007EN January 2016...

Page 10: ...This page is intentionally left blank 6 15 KV AND 25 KV CLASS EZ II SPLICE INSTALLATION INSTRUCTIONS MN650007EN January 2016...

Page 11: ...This page is intentionally left blank 7 15 KV AND 25 KV CLASS EZ II SPLICE INSTALLATION INSTRUCTIONS MN650007EN January 2016...

Page 12: ...on 2300 Badger Drive Waukesha WI 53188 United States Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN650007EN Rev 01 Supersedes 5000050839 Rev 03 SAFETY FOR...

Reviews: