A
B
AWG 24-12
0.2 - 2.5 mm
2
7 mm
(0.28“)
0.5 - 0.6 Nm
(5 - 7 lb-in)
3 Installation
27
ESR5-BWS-31-24VDC
11/23 MN049020EN Eaton.com
3.4.2 ?Wiring topic
▶
Connect the cables to the connection terminals with the help of a screw-
driver.
Figure 15:
Connection of the cables
Apply the nominal input voltage U
N
(24 V DC) to terminals A1/A2.
→
The
Power LED is lit.
Connect the sensor circuit as per the wiring to S11/S12/S22.
Automatic start
→
The signal current path 41/42 opens.
→
The enable current paths 13/14, 23/24 and 33/34 close.
→
The K1 and K2 LEDs are lit.
→
Ferrules are recommended when connecting flexible cables.
→
Use copper wire approved for temperatures of up to 60 °C /
75 °C in order to meet the requirements for the UL listing.