- 10 - 

supply. If the indicator is still off at this time, your ELC2 is malfunctioned. Send 
your ELC2 back to your distributor for repair. 

 

RUN indicator 

Check your ELC2 status. When ELC2 is running, this indicator will be on. You can 
use ELC-HHP, the ladder diagram editing program or the switch on the panel to 
RUN or STOP ELC2. 

 

ERROR indicator 

If you enter an incorrect program into ELC2 or use instructions or devices that 
exceed their range, this indicator will flash (approx. every 1 second). When this 
happens, you have to obtain the error code from D1004 and save the address 
where the error occurs in register D1137 (if the error is a general circuit error, the 
address of D1137 will be invalid). Find out the cause of the error, amend the 
program and resend the program to ELC2. If you cannot connect to ELC2 and this 
indicator keeps flashing quickly (approx. every 0.2 second), it means that the 24 
Vdc power voltage is insufficient. Please check if the 24V DC power supply is 
overloaded. 
If the ERROR indicator is on, you have to check the special relay M1008. If 
M1008 is on, it indicates that the execution time of program loop exceeds the 
preset time-out (in D1000). In this case, turn the RUN/STOP switch to STOP, 
check the special register D1008 and obtain the location in the program where the 
time-out takes place. Please refer to the WDT instruction to solve this problem. 
After amending the program, you only need to resend the program to stop the 
indicator from flashing. If the indicator still keeps flashing at this time, switch off 
the power and check if there is any interference existing or conductive matter 
inside ELC2. 
For details of error codes (in D1004, hex coding), see “ELC System Manual: 
Programming”. 

 

Input indicator 

On/Off of input point is indicated by input indicator or monitored by ELC-HHP. 
When the action condition of the input point is true, this indicator will be on. If 
abnormality is identified, check if the indicator and input circuit are normal. Use of 
electronic switch with too much electricity leakage often results in unexpected 
actions of the input point.   

 

Output indicator 

On/Off of output point is indicated by the output indicator. When the output 
indicator (On/Off) does not correspond to the action of its load, please be aware of 
the following: 

1.  The output contact may be melted or blocked due to an over loaded or 

short-circuited load, which will result in poor contact. 

2.  If you are suspicious that the output point may execute an undesired action, 

check the output wiring circuit and whether the screw is properly tightened. 

 

COM1, COM2, and USB indicators 

If the RS232/USB LED indicator is On, it means that COM1/the USB port is 
receiving data. 
If the RS485 LED indicator is On, it means that COM2 is sending data. 

 

Summary of Contents for ELC2 Series

Page 1: ...ELC2 Series Programmable Logic Controllers INSTRUCTION SHEET Applicable Controllers ELC2 PA20AADR ELC2 PA20AADT ELC2 PA20AADP 5012617501 PA21 2014 10 30 IL050004EN...

Page 2: ...Il doit tre install que dans une enceinte protectrice boitier armoire etc saine d pourvue de poussi re d humidit de vibrations et hors d atteinte des chocs lectriques La protection doit viter que les...

Page 3: ...t up C112 C127 16 points 2 C200 C223 24 points 1 32 bit count up down C224 C232 9 points 2 Total 233 points C235 C242 1 phase 1 input 8 points 2 Software C233 C234 2 phase 2 input 2 points 2 C243 C244...

Page 4: ...t points Y0 Y5 in ELC2 PA series ELC2 PA occupies 16 input points X0 X17 and 16 output points Y0 Y17 Extension input points start from X20 and extension output points start from Y20 4 If ELC2 PA is co...

Page 5: ...ELC2 PA20AADT UP ZP must work with external auxiliary power supply 24 Vdc 15 20 rated consumption approx 3mA point ELC2 PA20AADP UP ZP must work with external auxiliary power supply 5 30 Vdc rated con...

Page 6: ...T P 4 Analog Input 2 Analog output V0 I0 VI0 V1 I1 VI1 V2 I2 VI2 V3 I3 VI3 FE VO0 VO1 IO1 AG S S X0 X1 X2 X5 X6 X7 Y0 Y1 Y2 Y3 Y4 Y5 X4 C0 C1 IO0 X3 V0 I0 VI0 V1 I1 VI1 V2 I2 VI2 V3 I3 VI3 FE VO0 VO1...

Page 7: ...50 60Hz 2 Breaker 3 Emergency stop This button cuts off the system power supply when accidental emergency takes place 4 Power indicator 5 AC power supply load 6 Power supply circuit protection fuse 2...

Page 8: ...relay or transistor NPN PNP outputs Please note the connection of shared terminals when wiring output terminals 2 Output terminals Y0 Y1 and Y2 of relay models use C0 common port Y3 Y4 and Y5 use C1 c...

Page 9: ...e protection in case of any unexpected errors 8 Absorber To reduce the interference on AC load Figure 3 Transistor T output circuit wiring Transistor output NPN type for ELC2 PH12NNDT Transistor outpu...

Page 10: ...d to be connected to the client node and the last server node with resistor value of 120 2 To ensure communication quality please apply double shielded twisted pair cable 20AWG for wiring 3 When volta...

Page 11: ...e program where the time out takes place Please refer to the WDT instruction to solve this problem After amending the program you only need to resend the program to stop the indicator from flashing If...