 A/D and D/A External Wiring 

 A/D: Active 

 A/D: Passive 

V0+

I0+

VI0-

CH1

V3+

I3+

VI3-

CH3

0V

24V

FE

Voltage input

Current input

Shielded 

cable

Shielded 

cable

 
      Terminal 

power module

of 

Grounding (100     or less)

+

-

U

I N

+

-

U

I N

1

2

3

4

4

5

V0+

I0+

V0-

CH1

V3+

I3+

VI3-

CH3

FE

Voltage input

Current input

Shielded 

cable

Shielded 

cable

 

        Terminal of

power module

Grounding (100     or less)

-

+

U

IN

-

+

0V

24V

1

2

3

4

5

4

 D/A 

VO0

IO0

VO1

IO1

AG

CH1

Isolation wire

CH2

Voltage output

AC drive, recorder,

scale value...

AC drive, recorder,

scale value...

Current output

Isolation wire

6

7

4

4

8

8

 

Note: When the A/D module is 
connected to current signals, make 
sure to short-circuit “V+” and “I+” 
terminals.

 

 RS-485 Wiring 

D+ D- SG

D+ D- SG

SG D+ D-

3

4

1

2

2

3

4

 

1

 

Client node

 

2

Server node 

3

 

Terminal resistor 

4

Shielded cable 

Note: 1. Terminal resistors are suggested to be connected to the client node and the last server 

node with resistor value of 120

2. To ensure communication quality, please apply double shielded twisted pair cable 

(20AWG) for wiring. 

3. When voltage drop occurs between the internal ground references of two

 

systems, 

connect the systems with Signal Ground point (SG) for achieving equal potential 
between systems so that a stable communication can be obtained. 

 Precision of the RTC (Second/Month) 

Temperature 

(°C/°F) 

0/32 25/77 55/131 

Maximum error 

(Second) 

-117 52 -132 

Duration in which the RTC is latched: One week 

 

 Troubleshooting & Indicator Description 

Based on the indicators on the front panel, please check the following for errors: 

 

POWER indicator 

When ELC2 is powered, the POWER LED indicator on the front panel will be on 
(in green). If this indicator is not on or the ERROR indicator keeps flashing when 
ELC2 is powered indicates that the power 24V are insufficient or DC 
power supply 24V is overloaded. In this case, change another 24V DC power 

Summary of Contents for ELC2 Series

Page 1: ...ELC2 Series Programmable Logic Controllers INSTRUCTION SHEET Applicable Controllers ELC2 PA20AADR ELC2 PA20AADT ELC2 PA20AADP 5012617501 PA21 2014 10 30 IL050004EN...

Page 2: ...Il doit tre install que dans une enceinte protectrice boitier armoire etc saine d pourvue de poussi re d humidit de vibrations et hors d atteinte des chocs lectriques La protection doit viter que les...

Page 3: ...t up C112 C127 16 points 2 C200 C223 24 points 1 32 bit count up down C224 C232 9 points 2 Total 233 points C235 C242 1 phase 1 input 8 points 2 Software C233 C234 2 phase 2 input 2 points 2 C243 C244...

Page 4: ...t points Y0 Y5 in ELC2 PA series ELC2 PA occupies 16 input points X0 X17 and 16 output points Y0 Y17 Extension input points start from X20 and extension output points start from Y20 4 If ELC2 PA is co...

Page 5: ...ELC2 PA20AADT UP ZP must work with external auxiliary power supply 24 Vdc 15 20 rated consumption approx 3mA point ELC2 PA20AADP UP ZP must work with external auxiliary power supply 5 30 Vdc rated con...

Page 6: ...T P 4 Analog Input 2 Analog output V0 I0 VI0 V1 I1 VI1 V2 I2 VI2 V3 I3 VI3 FE VO0 VO1 IO1 AG S S X0 X1 X2 X5 X6 X7 Y0 Y1 Y2 Y3 Y4 Y5 X4 C0 C1 IO0 X3 V0 I0 VI0 V1 I1 VI1 V2 I2 VI2 V3 I3 VI3 FE VO0 VO1...

Page 7: ...50 60Hz 2 Breaker 3 Emergency stop This button cuts off the system power supply when accidental emergency takes place 4 Power indicator 5 AC power supply load 6 Power supply circuit protection fuse 2...

Page 8: ...relay or transistor NPN PNP outputs Please note the connection of shared terminals when wiring output terminals 2 Output terminals Y0 Y1 and Y2 of relay models use C0 common port Y3 Y4 and Y5 use C1 c...

Page 9: ...e protection in case of any unexpected errors 8 Absorber To reduce the interference on AC load Figure 3 Transistor T output circuit wiring Transistor output NPN type for ELC2 PH12NNDT Transistor outpu...

Page 10: ...d to be connected to the client node and the last server node with resistor value of 120 2 To ensure communication quality please apply double shielded twisted pair cable 20AWG for wiring 3 When volta...

Page 11: ...e program where the time out takes place Please refer to the WDT instruction to solve this problem After amending the program you only need to resend the program to stop the indicator from flashing If...

Reviews: