Holding Register 

Device 

type 

Explanation 

Modbus address 

(Hex) 

6-digit Modbus 

address (Dec) 

Number 

BR Basic 

Register 0x0000~0x0040  400001~400064 

64 

T Timer 

(word) 

0x1600~0x160F 405633~405649  16 

C Counter 

(word) 

0x1E00~0x1E0F  407681~407696  16 

RCR 

CR of extension 

modules 

0x3000~0x3190 412289~412689  400 

 

ƒ

 EtherNet/IP Parameters 



 Service Codes Supported 

Service code 

Explanation 

Object supported 

0x05 Reset 

Identity 

Object 

0x0E Get 

Attribute 

Single 

Identity Object 
Message Router Object 
Assembly Object 
Connection Manager Object 
Discrete Input Object 
Discrete Output Object 
BR Object 
RCR Object 
TCP/IP Interface Object 
Ethernet Link Object 

0x10 Set 

Attribute 

Single 

Assembly Object 
Discrete Output Object 
BR Object 
RCR Object 

0x4E 

Forward Close 

Connection Manager Object 

0x54 

Forward Open 

Connection Manager Object   



 Object and Instance Supported 

Object 

Class 

Code 

Instance 

Code 

Explanation 

Identity Object 

0x01 

#1 ~ #7 

CIP Identity* 

Message Router Object 

0x02 

#1 

Application message router* 

Assembly Object 

0x04 

#100 Input 

point 

assembly 

#101 Output 

point 

assembly 

#102 

RCR read mapping assembly 

#103 

RCR write mapping assembly 

#104 

Input point and RCR read 
mapping assembly 

#105 

Output point and RCR write 
mapping assembly 

Connection Manager 
Object 

0x06 

#1 

Application connection manager* 

Summary of Contents for ELC Series

Page 1: ...2010 12 03 5011696801 ETP1 Eaton Logic Controller Ethernet Distributed I O Adapter Module INSTRUCTION SHEET Applicable Distributed I O Adapter Module ELC CAENET IL05006001E 002 1214120 01...

Page 2: ...t unless power has been switched off or the area is known to be non hazardous a DO NOT connect AC power to any of the DC input output terminals as it will damage them Check all wiring prior to power u...

Page 3: ...icator on ELC CAENET is ON 2 Analog I O modules in RUN status 3 Smart PLC function is running RUN STOP 1 Analog I O modules switch from RUN to STOP status 2 Output points on digital I O modules are al...

Page 4: ...ransmission Rate 10 100 Mbps Auto Detect Protocol ICMP IP TCP UDP DHCP NTP HTTP MODBUS TCP EtherNet IP RS 232 Interface Interface RS 232 Number of Ports 1 Port Transmission Cable ELC CBPCELC3 RS 485 I...

Page 5: ...re 5 95 humidity Vibration Shock Resistance Standard IEC61131 2 IEC 68 2 6 TEST Fc IEC61131 2 IEC 68 2 27 TEST Ea Certificates Installation How to connect extension modules to the ELC CAENET 1 Adjust...

Page 6: ...on Codes Supported Exception code Explanation 0x01 Illegal function 0x02 Illegal data address 0x03 Illegal data value 0x04 Slave device failure 0x0A Gateway path unavailable 0x0B Gateway target device...

Page 7: ...t Object Discrete Output Object BR Object RCR Object TCP IP Interface Object Ethernet Link Object 0x10 Set Attribute Single Assembly Object Discrete Output Object BR Object RCR Object 0x4E Forward Clo...

Page 8: ...tched to RUN BAT LOW Red constantly OFF The battery is normal None Red flashes The battery is in low voltage Check the battery RS 232 Yellow flashes Data is being transmitted in the serial port None Y...

Page 9: ...connection Check if the number of connections exceeds the maximum F7 Flash RS 485 setting error Check if the RS 485 communication format is correct F8 Flash IP setting error 1 DHCP request failure 2 I...

Page 10: ...le to locate a module Not connected to the network Check if ELC CAENET is correctly connected to the network Unable to locate a module The computer is blocked by the firewall Search by IP address or u...