EGR-5000
Quick Start Guide
36
Double click on “Pickup” in the “Protection
Para/Set 1/51P[1}-Phase Inst. OC” dialog
box and the screen shown to the left will
appear.
The up and down arrows allows the User to
change the “Pickup” In setting. The value
range available is 0.02 to 40.00 In. Once
the desired setting has been selected, click
on the “OK” button. An asterisk will appear
next to the modified parameter.
To save the all the modified Protection
Parameters, click on “File”, “Save”, then
“OK”. Once the file has been saved, the
asterisks will disappear from in front of the
modified parameter(s).
This procedure can be used to save any
changed parameters during the entire
PowerPort-E device set-up process.
To transfer parameters to the device, make
the appropriate selection from the “Device”
pull-down menu. The User has the option of
downloading all settings or only those
modified. Note that if settings were not
originally uploaded from the device and the
User downloads all parameters, then the
defaults for the unmodified parameters will
overwrite the parameters currently stored in
the device. Transferring only modified
parameters is the safer option.