Edison™ Single-Phase Vacuum Capacitor Switch

InstallatIon and operatIon InstructIons

   MN230007EN   February 2017

Table 3 .  Dimensions for Figure 5 drawings

Switch Open Contact 

BIL/L-G BIL

Dimensions, inches (mm)

Creepage, inches (mm)

A*

B*

C*

Terminal to Terminal Terminal to Ground

95/95 kV BIL

27.78 (706)

25.89 (659)

17.69 (449)

17.3 (440)

19.6 (498)

95/125 kV BIL

27.78 (706)

25.89 (659)

17.69 (449)

23.6 (600)

24.0 (610)

125/125 kV BIL

30.54 (776)

28.81 (732)

17.69 (449)

32.0 (813)

24.0 (610)

125/150 kV BIL

32.54 (827)

30.81 (783)

19.69 (500)

32.0 (813)

32.0 (813)

* See Figure 5 on page 6.

Service information

Service requirements

The mechanical durability of the Edison capacitor switch 

was demonstrated by completing a minimum of 50,000 

operations after performing the Mechanical Life Test in 

accordance with IEEE Std C37.66™-2005 standard. The 

switch requires no routine maintenance; however, the 

switch should be inspected on a regular basis to check for 

physical damage and to verify operation.

Frequency of inspection

Because these switches are applied under widely varying 

operation and climatic conditions, maintenance intervals 

are best determined by the user based upon actual 

operating experience.

   WARNING

Hazardous voltage . The switchgear (apparatus and 

control) and high-voltage transformer must be in a test 

cage or similar protected area to prevent accidental 

contact with the high-voltage parts . 

Solidly ground all equipment . Failure to comply can 

result in death, severe personal injury, and equipment 

damage . 

T221 .5

CAUTION

Radiation . At voltages up to the specified test voltages, 

the radiation emitted by the vacuum interrupter is 

negligible . However, above these voltages, radiation 

injurious to personnel can be emitted . See Service 

Information S280-90-1, 

Vacuum  Interrupter Withstand 

Test Voltage Ratings Information

, for further information . 

 

G109 .2

Summary of Contents for Edison Cooper Power Series

Page 1: ...Edison Single Phase Vacuum Capacitor Switch Installation and Operation Instructions COOPER POWER SERIES Vacuum Switches MN230007EN Effective February 2017 Supersedes November 2016...

Page 2: ...TICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUM...

Page 3: ...initial inspection 1 Handling and storage 1 Standards 1 Quality standards 1 Description of operation 1 RATINGS AND SPECIFICATIONS 2 Check switch ratings before installation 2 Ratings 2 INSTALLATION P...

Page 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Page 5: ...e Acceptance and initial inspection Each capacitor switch is completely assembled inspected tested and adjusted at the factory It is in good condition when accepted by the carrier for shipment Upon re...

Page 6: ...king peak current A 15 000 15 000 15 000 15 000 Symmetrical fault making current A 6 000 6 000 6 000 6 000 Withstand peak current A 15 000 15 000 15 000 15 000 Short time symmetrical withstand current...

Page 7: ...NG This equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death se...

Page 8: ...actuators wired for two and three wire controls are shown in Figure 2 Accessories are shown with dashed lines These diagrams apply only for alternating current ac control voltage For direct current d...

Page 9: ...he sleet hood as shown in Figure 3 and Figure 4 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle it does not ensure that the line has been de energized Always...

Page 10: ...7 Dimensions 15 kV 95 95 kV BIL 200A 15 kV 95 125 kV BIL 200A 15 kV 125 125 kV BIL 400A 25 kV 125 125 kV BIL 200A 15 kV 125 150 kV BIL 400A 25 kV 125 150 kV BIL 200A Figure 5 Dimensions of Edison capa...

Page 11: ...tch requires no routine maintenance however the switch should be inspected on a regular basis to check for physical damage and to verify operation Frequency of inspection Because these switches are ap...

Page 12: ...ted States Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN230007EN February 2017 Eaton is a registered trademark All trademarks are property of their respec...

Reviews: