2

Edison™ Single-Phase Vacuum Capacitor Switch

InstallatIon and operatIon InstructIons

   MN230007EN   February 2017

Ratings and specifications

Check switch ratings before installation

The Edison capacitor switch must be applied within its 

specified ratings. Check data plate ratings and compare with 

the system characteristics at the point of application prior to 

installation. Table 1 list the ratings and specifications for the 

Edison capacitor switch.

Ratings

All ratings meet or exceed values in IEEE Std C37.66™-2005 

standard for a distribution-class switch, where applicable.

Table 1 .  Ratings and specifications

Voltage class

Switch type

15 kV

ECS15-95

ECS15-125

25 kV

ECS25-125

ECS25-150

Rated maximum voltage, 50/60 Hz 

Ungrounded capacitor banks, L-L (kV)

15.6

15.6

25

15.6

Solidly grounded capacitor banks, L-L (kV)

15.6

27

25

38

Impulse withstand voltage

Open contact kV (BIL)

95

95

125

125

Line to ground (kV BIL)

95

125

125

150

Withstand voltage, 60 Hz

Power Frequency Dry Withstand (kV)

60

60

60

70

Power Frequency Wet Withstand (kV)

50

50

50

60

Continuous current 50/60 Hz (A)

200

200/400

200

200

Capacitive switching current 50/60 Hz (A)

200

200/400

200

200

Fault making peak current (A)

15,000

15,000

15,000

15,000

Symmetrical fault making current (A)

6,000

6,000

6,000

6,000

Withstand peak current (A)

15,000

15,000

15,000

15,000

Short-time symmetrical withstand current (A)

4,500

4,500

4,500

4,500

High frequency transient making peak current (A)

9,000

9,000/12,000 

*

9,000

9,000

Rated transient inrush frequency (Hz)

6,000

6,000

6,000

6,000

Creepage distance

Terminal to terminal (mm)

440

600

813

813

Terminal to ground (mm)

498

610

610

813

Operating voltage range, 50/60 Hz 

**

110/120 Vac (V)

75 – 130

75 – 130

75 – 130

75 – 130

240 Vac (V)

150 – 260

150 – 260

150 – 260

150 – 260

Nominal control current

110/120 Vac for 100 msec (A)

9

9

9

9

240 Vac for 100 msec (A)

6

6

6

6

Weight (lb/kg)

32/14

33/15

33/15

34/16

Operating temperature range

-40 °C to +60 °C

-40 °C to +60 °C

-40 °C to +60 °C

-40 °C to +60 °C

Mechanical operations

50,000

50,000

50,000

50,000

 

*

 

The 15.6 kV rated Edison Capacitor Switch is available with an optional High Frequency Transient Making Peak Current of 12 kA. Contact factory for additional information.

 

** Contact factory for more information regarding dc control voltages.

otee:

N

The durability of the Edison capacitor switch was demonstrated by completing a minimum of 50,000 mechanical 

operations after performing the Mechanical Life Test in accordance with IEEE Std C37.66™-2005 standard. One 

operation is defined as one close and one open operation. 

Summary of Contents for Edison Cooper Power Series

Page 1: ...Edison Single Phase Vacuum Capacitor Switch Installation and Operation Instructions COOPER POWER SERIES Vacuum Switches MN230007EN Effective February 2017 Supersedes November 2016...

Page 2: ...TICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUM...

Page 3: ...initial inspection 1 Handling and storage 1 Standards 1 Quality standards 1 Description of operation 1 RATINGS AND SPECIFICATIONS 2 Check switch ratings before installation 2 Ratings 2 INSTALLATION P...

Page 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Page 5: ...e Acceptance and initial inspection Each capacitor switch is completely assembled inspected tested and adjusted at the factory It is in good condition when accepted by the carrier for shipment Upon re...

Page 6: ...king peak current A 15 000 15 000 15 000 15 000 Symmetrical fault making current A 6 000 6 000 6 000 6 000 Withstand peak current A 15 000 15 000 15 000 15 000 Short time symmetrical withstand current...

Page 7: ...NG This equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death se...

Page 8: ...actuators wired for two and three wire controls are shown in Figure 2 Accessories are shown with dashed lines These diagrams apply only for alternating current ac control voltage For direct current d...

Page 9: ...he sleet hood as shown in Figure 3 and Figure 4 WARNING Hazardous voltage Do not rely on the open position of the yellow operating handle it does not ensure that the line has been de energized Always...

Page 10: ...7 Dimensions 15 kV 95 95 kV BIL 200A 15 kV 95 125 kV BIL 200A 15 kV 125 125 kV BIL 400A 25 kV 125 125 kV BIL 200A 15 kV 125 150 kV BIL 400A 25 kV 125 150 kV BIL 200A Figure 5 Dimensions of Edison capa...

Page 11: ...tch requires no routine maintenance however the switch should be inspected on a regular basis to check for physical damage and to verify operation Frequency of inspection Because these switches are ap...

Page 12: ...ted States Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN230007EN February 2017 Eaton is a registered trademark All trademarks are property of their respec...

Reviews: