Technical data EC4E
53
09/08 AWB2724-1614en
Peak short-circuit current
A
16
Thermal cutout
Max. operating frequency at constant resistive load
R
L
< 100 k
O
(dependant on program and load)
ops/h
Parallel connection of outputs
With resistive load, inductive load
with external suppressor circuit,
combination within a group
Number of outputs
max.
4
Max. total current
A
2 (Caution: Outputs must be
actuated simultaneously and
for the same time duration)
Status indication of the outputs
LCD display (if provided)
Inductive load
Without external suppressor circuit
1)
T
0.95
=
1
ms,
R
=
48
O
,
L
=
16
mH
Utilization factor
g
0.25
Duty factor
% DF
100
Max. operating frequency
f
=
0.5 Hz (max. DF = 50 %)
Operations
1500
DC-13,
T
0.95
=
72
ms,
R
=
48
O
,
L
=
1.15
H
Utilization factor
g
0.25
Duty factor
% DF
100
Max. operating frequency
f
=
0.5 Hz (max. DF = 50 %)
Operations
1500
T
0.95
=
15
ms,
R
=
48
O
,
L
=
0.24
H
Utilization factor
g
0.25
Duty factor
% DF
100
Max. operating frequency
f
=
0.5 Hz (max. DF = 50 %)
Operations
1500