![Eaton EC4E-221-6D4T1 Hardware And Engineering Download Page 45](http://html2.mh-extra.com/html/eaton/ec4e-221-6d4t1/ec4e-221-6d4t1_hardware-and-engineering_3919340045.webp)
41
09/08 AWB2724-1614en
5
Operation
The device’s operating state is indicated by two LEDs on the
device front. Their meaning is described in the tables below.
Table 3:
CAN-LED-status indicator
CAN LED
Colour
Meaning
OFF
Red
Device is operational (no fault).
Single flash
Red
At least one of the error counters of the CAN controller
has reached or exceeded the warning level (too many
error frames).
Flashing
Red
Auto Baudrate detection inprogress or LSS services in
progress (Alternately flashing
with
RUN-LED)
Double flash
Red
A guard event (NMT-Slave or NMT-master) or a
heartbeat event (Heartbeat consumer) has occurred.
Triple flash
Red
The SYNC message has not been received within the
configured communication cycle period time out (see
Object
Dictionary
Entry
0x10
06).
Illuminated
Red
The CAN controller is bus off
Flashing
Green
Auto baudrate detection in progress or LSS services in
progress (Alternately flashing with ERROR LED)
Single
flash
Green
Device is in STOPPED state
Flashing
Green
Device is in PREOPERATIONAL state
Illuminated
Green
Device is in OPERATIONAL state
h
The CAN LED flashes orange if operational and fault states
occur at the same time. This is the case, for example, when
the device is operational (green light) and has reached an
error count limit (flashing red). This results in an orange
flashing alternating with green.