ATS-00_EN
4. Power cables connection
4.2 Access to terminal blocks EATS30N - EATS30H
4.3 Hardwired Input/Output connection (EU) EATS30N - EATS30H
To load
To UPS 2
To UPS 1
1
. Connect input power cables to two
UPSs (UPS1 (S1) is the preferred
source).
2
. Connect output power cable to
load.
Cable cross sections
Terminal
position
Wire
function
Terminal wire
size rating
Minimum input
wire size
Tightening
torque
L1 / L2
Phase
32A
10 AWG
14Kgf-cm
N1 / N2
Neutral
Ground
4.4 Input/Output connection (US) EATS30P
To load
To UPS 2
To UPS 1