92
Fault code: F305
Fault lamp lights long,
Beep continuous.
Indicates that the UPS
rectifier fault.
Please contact your supplier
Fault code: A307
Fault lamp lights long,
Beep continuous.
Indicates that the UPS
rectifier fuse fault.
Please contact your supplier
Fault code: F805
Fault lamp lights long,
Beep continuous.
Indicates that the UPS
has detected
abnormally low
impedance placed on
its output and considers
it a short circuit
Remove all the loads. Turn off
the UPS.
Check if UPS output and loads
is short circuit.
Ensure short circuit is removed
before turning on again.
Fault code: F70D
Fault lamp lights long,
Beep continuous.
Indicates that the UPS
get invert over voltage
fault
Remove some equipment from
the UPS, clear the fault code
and try restart again.
Fault code: F70C
Fault lamp lights long,
Beep continuous.
Indicates that the UPS
get inverter under
voltage fault
Remove some equipment from
the UPS, clear the fault code
and try restart again.
Fault code: F704
Fault lamp lights long,
Beep continuous.
Indicates that the UPS
inverter fault
Please contact your supplier
Fault code: A80E
Fault LED is flash
2 beep every 1 second
Power requirements
exceed the UPS
capacity
Remove some of the
equipment from the UPS.
The UPS continues to operate,
but may switch to Bypass
mode or shut down if the load
increases.
The alarm resets when the
condition becomes inactive.
Fault code: A810
Fault LED is flash
2 beep every 1 second
Overload fault
Remove some of the
equipment from the UPS.
Check if it is fault for the
equipment.
Summary of Contents for DXRT 10KS31-IN Series
Page 1: ...Eaton DXRT 10KXL31 系列 系列 系列 系列 在线式 UPS ...
Page 11: ...10 4 安装尺寸图参考如下 塔式安装 1 从附件中取出脚架 向下扣成脚架 2 将LCD面板从箱体上拔出适当高度 20 30mm ...
Page 14: ...13 2 安装挂耳 注意挂耳安装方向 凹形向下 3 按如下图所示方向将 UPS 主机和电池箱放入到机架的滑道上 然后推到固定 位置 从附件中取出螺钉 将其固定在即加上 ...
Page 32: ...31 清除事件记录 该指令可以清除事件子菜单中的所有记录 请谨慎 恢复出厂设置 所有的设置将会恢复到默认的出厂状态 该指令只能在旁 路下执行 ...
Page 34: ...33 ...
Page 35: ...34 说明 如何设置输出电压 ...
Page 43: ...42 Eaton DXRT 10KS31 IN Series Online UPS ...
Page 54: ...53 2 5 Circuit diagram ...
Page 83: ...82 ...
Page 85: ...84 Example set rated output voltage value ...
Page 86: ...85 ...
Page 98: ...0 614 40029 00 ...