4
●
Electrical performance
Input
Model
Voltage
Frequency
Power Factor
6000L(XL)/
10000L(XL)
Single-phase
(46~54)/(56~64)Hz
>0.98 (Full load)
●
Operating environment
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following :
Output
Voltage
regulation
Power
factor
Frequency
tolerance
Distortion Overload capacity
Current
crest ratio
±
4%
0.7lag
Synchronized
(46~54)/(56~64)Hz
in Line mode(AC
mode)
±
0.1% of normal
frequency in
Battery mode.
THD<3%
Full load
(linear
load)
105%
~
130% load
transfers to bypass
mode after 10
minutes.
>130% load transfers
to bypass mode after
1 second and
shutdown the output
after 1 minutes
3:1
maximum
Temperature
Humidity
Altitude
Storage temperature
0
℃
~40
℃
<95%
<1000m
-15
℃
~40
℃
Altitude (M)
1000
1500 2000 2500 3000 3500 4000 4500 5000
Deratingpower 100% 95% 91% 86% 82% 78% 74% 70% 67%