background image

25

Instruction Book    

IB182942EN   July 2018   www.eaton.com

DST-2-VR

+

VR-Series

+

 Replacement Circuit Breaker

5.11.3   5kV Rtmoval Proctdurt (DST-2-5-VR

+

 250, Domtstic 

and Canadian Rotary Racking Vtrsion)

a.  To remove the circuit breaker from the cell, verify that the breaker 

is in the “OPEN” position and the motor cutoff switch is in the 

“OFF” position. Place the rotary racking handle on the rotary 

racking hex head. Rotate the racking handle counter-clockwise 

to move the circuit breaker from the “connect” position to the 

“Disc/Test” position. As the circuit breaker leaves the “connect” 

position, the shutters will start to close after the primary 

disconnects have cleared, isolating the breaker from the line and 

load connections. Continue rotating the racking handle counter-

clockwise until the position indicators on the breaker indicate 

the “Disc/Test” position and it is not possible to turn the racking 

handle with normal force. (Damage to the circuit breaker will 

occur if the racking handle is forced counter-clockwise beyond this 

point of resistance.) In this position, the secondary disconnect 

control power connections can be re-connected so the breaker 

can be operated either electrically or manually. Remove the 

racking handle prior to performing and breaker tests.

otte:

N

For Canadian versions with separate “disconnect” and “test” positions, 

it will stop first at the “test” position. Electrical and mechanical tests of the 

circuit breaker can be performed in this position. Remove the racking handle 

prior to performing any breaker test.

b.  If the circuit breaker is to be withdrawn from the cell, remove the 

rotary racking handle, and depress the interlock petal while pulling 

the breaker out of the circuit breaker compartment using the 

handles on the front of the breaker.

otte:

N

 For Canadian versions with separate “disconnect” and “test” 

positions, it will be necessary to remove the racking handle, step on the 

interlock petal and pull the circuit breaker to the next mechanical stop. At 

that mechanical stop, the circuit breaker is in the “disconnect” position. 

Stepping on the interlock petal again will release the circuit breaker so that 

it can be pulled to the fully withdrawn position and out of the circuit breaker 

compartment.

c.  During this travel from the “Disc/Test” position, the circuit 

breaker closing springs will discharge automatically with a loud 

noise similar to the noise made when the circuit breaker is 

closed. At this point, the breaker will be open with the springs 

discharged..

otte:

N

If through-the-door racking is desired, the cell door must be modified 

by cutting a hole in it which aligns with the rotary racking hex head. A sub-

cover must also be installed to block access to the racking hex head until 

required. Even with this modification, it will be necessary to position the 

circuit breaker compartment door open. Only after doing that, can closed door 

racking be performed from the “test” position to the “connect” position. 

The motor disconnect switch can be accessed while the door is open for 

installation or removal process, or flipped on or off with the racking handle.

5.11.4   15kV Instrtion Proctdurt (DST-2-15-VR

+

 500/750 

Domtstic and Canadian Rotary Racking Vtrsion)

a.  Verify that the circuit breaker racking system is in the fully 

withdrawn position. This is an important step, as breaker 

maintenance outside the breaker compartment may have required 

that the rotary racking be racked-in so that the circuit breaker 

could be closed. It must be returned to the fully withdrawn 

condition prior to insertion in the circuit breaker compartment.

b.  From the withdrawn position, align the center groove of the 

breaker wheels with the guide rails of the cell.

c.  Check that the closing spring status is located on the lower cover 

where it can be easily accessed (See Figure Set 3.3). Position the 

switch to “OFF” before inserting the breaker into the cell.

d.  Push the circuit breaker into the cell until the mechanical stop is 

reached; this will be indicated by an audible click. At this point, 

the front plunger has fallen in the front slot of the guide rail. In 

this position, the breaker can be operated. This position can also 

be verified by noting that the foot petal moves upward as the 

mechanical stop drops into the slot in the floor mounted rail. The 

racking hex head access handle is also released so that it can be 

raised for rotary racking. (Figure 5.5)

Figurt 5.6. Lifting Racking Acctss Handlt

otte:

N

For Canadian versions with separate “disconnect” and “test” positions, 

it will be necessary to step on the racking unlock petal and push the circuit 

breaker to the next mechanical stop. At that mechanical stop, the circuit 

breaker is in the “test” position. Provisions in the racking system prevents 

the circuit breaker from being un-latched and pushed beyond this mechanical 

stop; any additional movement toward the “connect” position must be 

achieved with the rotary racking feature. With the circuit breaker in the “test” 

position, item (e.) below can then be performed.

e.  In the “Disc/Test” position, the breaker can be operated manually 

and electrically, thus allowing maintenance tests or checks. To 

operate the breaker electrically, the secondary control block must 

be engaged at this time. The slider is located on the lower right 

hand area of the circuit breaker frame. If electrical testing is 

desired at this stage, engage the secondary control block slider 

by releasing the slide latch and pushing the slider toward the rear 

several inches. Push firmly on the front side of the slider until the 

contact block engages with the corresponding cell receptacle. 

Return the manual motor cutoff switch to the “ON” position. The 

spring charging motor will energize and charge the closing spring. 

The breaker is now in the “Test” position, with control voltage 

applied, and ready for electrical or manual testing.

 NOTICE

ONCE THE SECONDARY DISCONNECT BLOCK IS ENGAGED IN THE “TEST” 

POSITION, IT WILL REMAIN CONNECTED THROUGHOUT FURTHER INWARD 

MOVEMENT AS THE BREAKER ADVANCES FROM THE “DISC/TEST” TO THE 

“CONNECT” POSITION.

THE SPRING CHARGING MOTOR WILL ENERGIZE, IF THE MOTOR CUT-OFF 

SWITCH IS IN THE “ON” POSITION (FIGURE SET 3.3), AND CHARGE THE 

CLOSING SPRINGS AS THE SECONDARY CONNECTION IS MADE AS LONG 

AS CONTROL POWER IS AVAILABLE.

f.  From the “Disc/Test” position, the breaker can be advanced to the 

“connect” position. It is NOT necessary to step on the racking 

unlock foot petal when the circuit breaker is in this position. Lift 

the racking access handle by pulling it up and over to the right 

to gain access to the racking hex head. 

(This sttp must bt 

ptrformtd prior to clostd door racking.) 

The handle will be 

retained allowing full exposure of the racking hex head. PLace 

the rotary racking handle onto the rotary racking hex head. Turn 

the rotary racking handle clockwise until the “connect” position 

is reached and the handle can no longer be turned, as indicated 

on the switchgear floor mounted breaker position indicator, Figure 

5.6. 

Do not forct tht rotary racking handlt btyond this point 

as brtaktr damagt will occur.

Summary of Contents for DST-2-15-500

Page 1: ...Instruction Book IB182942EN DST 2 VR VR Series Replacement Circuit Breaker DST 2 VR 250 2000A Shown July 2018 Supersedes March 2018 Effective...

Page 2: ...ions of this equipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of particular eq...

Page 3: ...ERATION CHECK 21 5 4 VACUUM INTERRUPTER INTEGRITY 21 5 5 LOW FREQUENCY WITHSTAND TEST INSULATION CHECK 21 5 6 CONTACT EROSION AND WIPE 21 5 7 PRIMARY CIRCUIT RESISTANCE 21 5 8 ELECTRICAL OPERATIONS CH...

Page 4: ...portant that this installation and maintenance instruction booklet be read and followed closely to achieve optimum performance and a long useful circuit breaker life in its application 1 1 VISUAL INST...

Page 5: ...Latching Momentary Capabilities kV MVA Amps K Low Freq kV RMS Impulse kV Peak I kA RMS KI kA RMS kA RMS Peak DST 2 7 5 500 DST 2 7 5 VR 500 8 25 500 1200 2000 1 25 36 95 33 41 66 111 DST 2 15 500 DST...

Page 6: ...on com DST 2 VR VR Series Replacement Circuit Breaker Table 2 DST 2 VR Dimensions Circuit Breaker Type Existing Circuit Breaker Rated Continuous Current at 60 Hz Amps A B C D E F DST 2 VR 1200 2000 65...

Page 7: ...est coupler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death severe personal injury equipment damage and or improper operation Do not work on a close...

Page 8: ...and other components If damaged or loss is detected file claims immediately with the carrier and notify an Eaton representative Tools and Accessories Maintenance Tool Style 94C9506G01 This tool is us...

Page 9: ...ition before placing it in to storage The circuit breaker is shipped with its contacts open and closing springs discharged The indicators on the front cover should confirm this Insert the end of the m...

Page 10: ...w of DST 2 VR Front External View 1 Lock Out Tag Out 5 Manual Charging Socket 9 Push To Close Button 2 Levering In Access 6 Spring Charged Discharged Indicator 10 Interlock Pedal 3 Handle 7 Operations...

Page 11: ...T 2 VR VR Series Replacement Circuit Breaker Figure 3 3 b Rear External View of DST 2 VR Rear External View 1 Lifting Points 4 Anti Rotation Self Adjuster Optional 2 Secondary Disconnects 5 Ground Con...

Page 12: ...t is assembled at the factory as a unit to assure correct dimensional relationships between working components Three interrupter assemblies are used per circuit breaker Each vacuum interrupter assembl...

Page 13: ...ER CONTACTS ARE CLOSED OR THE CLOSING SPRINGS ARE CHARGED THE CIRCUIT BREAKER CONTACTS MAY OPEN OR THE CLOSING SPRINGS DISCHARGE CAUSING CRUSHING INJURY DISCHARGE THE SPRINGS AND OPEN THE CIRCUIT BREA...

Page 14: ...This is the anti pump function 4 4 1 TIMING The opening and closing times for the circuit breakers vary depending upon the control voltage power rating environment and test equipment Differences in ti...

Page 15: ...est and Connect positions OPERATION C and NO C and NC C and NO C and NO C and NC C and NO Brown Switch Black Switch Black Switch Brown Switch SWITCH TERMINAL LS1 bb LS2 aa LS2 bb LC PS1 PS2 Circuit Br...

Page 16: ...ring system tripping and spring release interlocks perform the following a Set the breaker mechanically trip free during the first 4 inches of travel into the cell and whenever the breaker receives a...

Page 17: ...Cover Removed VR Series Circuit Breaker Element Mechanism 1 LH Closing Spring 5 Spring Release Assembly 9 Manual Charge Socket 2 Latch Check Switch To Rear of Motor Cutoff Switch 6 Shunt Trip Assembly...

Page 18: ...eaker Closed Springs Charged 2 1 3 4 5 6 7 8 9 10 11 12 13 14 Closing Cam and Trip Linkage 1 Spring Release Close Latch 6 Ratchet Wheel 11 Anti Close Interlock 2 Pole Shaft 7 Spring Crank 12 Motor Rat...

Page 19: ...2 Main Link 6 Cam Shaft 10 Trip Latch Reset Spring 3 Operating Rod 7 Banana Link 11 Shunt Trip Lever 4 Pole Shaft 8 Trip latch 12 Shunt Trip Coil 4 1 2 3 5 6 7 8 9 10 11 12 4 8 a Circuit Breaker Open...

Page 20: ...a cell containing an MOC until after the switch has been properly adjusted WARNING MEASUREMENTS AND ADJUSTMENTS SHOULD NEVER BE ATTEMPTED IN AN ENERGIZED STRUCTURE IF THE STRUCTURE CANNOT BE DE ENERGI...

Page 21: ...YS REMOVE THE MAINTENANCE TOOL AFTER CHARGING THE SPRING FAILURE TO REMOVE THE MAINTENANCE TOOL FROM THE BREAKER COULD CAUSE INJURY TO PERSONNEL AND OR EQUIPMENT DAMAGE IF THE BREAKER WAS TO CLOSE Clo...

Page 22: ...n The test position can be verified by the inability to move the breaker in or out the Interlock Pedal is in the up position and the cell label test is visible on the floor of the cell in front of the...

Page 23: ...onnect position can be verified by the inability to move the breaker in or out the Interlock Pedal is up and has released the trip mechanism and the cell label operating is visible on the floor of the...

Page 24: ...s DISCHARGED and that the main contact status indicator reads OPEN Manually trip close and trip the breaker as needed to obtain this status Note N The motor cutoff switch is located on the lower cover...

Page 25: ...so that the circuit breaker could be closed It must be returned to the fully withdrawn condition prior to insertion in the circuit breaker compartment b From the withdrawn position align the center g...

Page 26: ...al of the circuit breaker Note N For Canadian versions with separate disconnect and test positions it will stop at the test position Electrical and mechanical tests of the circuit breaker can be perfo...

Page 27: ...and retest or replace Insulation Integrity Main circuit to ground Withstand 15kV 60Hz for 1 Minute 5kV Rating Hi pot Tester Clean and retest or replace Control circuit to ground Charging Motor discon...

Page 28: ...ommended that the equipment be capable of delivering 25 milliamperes for one minute The current delivery capability of 25 mA ac applies when all three vacuum interrupters are tested in parallel If ind...

Page 29: ...ressed in micro ohms Repeat for the remaining two poles The resistance should not exceed the factory test levels more than 200 as stated in IEEE C37 09 Factory test levels are recorded on the circuit...

Page 30: ...ol Mounting Testing Locations by Circuit Breaker Type CIRCUIT BREAKER DESIGNATION APPROXIMATE MECHANISM CHASSIS WIDTH INCH LOWER MOUNTING HOLE LOWER MOUNTING HOLE MARKER PLACEMENT HOLE VR Series 18 A1...

Page 31: ...a sheet of paper that can be kept as a record of the test Record the date of the test person conducting the test circuit breaker serial number and the operations counter on the tape or paper Figures 6...

Page 32: ...Marker Interface Cam Marker CloSure Tool TM 15 O 15 O Figure 6 13 Determining the Distance Traveled Figure 6 14 Illustrative Testing Tape Sample Figure 6 12 Evaluate the CloSure Performance Date of Br...

Page 33: ...nt requires maintenance only once every ten years or ten thousand operations which ever comes first After a ten year service interval or when ten thousand operations have been reached contact your loc...

Page 34: ...urned Motor Cut Off Contacts open or burned Trip Coil Assembly Clapper fails to reset Closing sound but no close Pole Shaft Not open fully Trip Latch Reset Spring Damaged or missing Trip Bar D Shaft F...

Page 35: ...SWITCH Circuit Breaker Auxiliary Switch 94C9525G13 5 POSITION SWITCH Circuit Breaker Position Switch PS1 94C9525H06 6 POSITION SWITCH Circuit Breaker Position Switch PS2 94C9525H07 7 LATCH CHECK SWITC...

Page 36: ...ulevard Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No IB182942EN July 2018 Eaton is a registered trademark All trademarks are property of thei...

Reviews: