9 Appendix
9.5 accessories
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
223
9.5.2 Protection, overload relay, optional mains contactor
Part no.
Soft starter function with soft stop in case of overload
Optional mains contactor
Line protection
1)
Overload relays2
)
DS7-34xSX004N0-…
PKM0-4 (+ CL-PKZ0)
3)
ZB12-4
DILM7
DS7-34xSX007N0-…
PKM0-10 (+ CL-PKZ0)
ZB12-10
DILM9
DS7-34xSX009N0-…
PKM0-10 (+ CL-PKZ0)
ZB12-10
DILM9
DS7-34xSX012N0-…
PKM0-12 (+ CL-PKZ0)
ZB12-12
4)
DILM12
DS7-34xSX016N0-…
PKM0-16 (+ CL-PKZ0)
ZB32-16
DILM17
DS7-34xSX024N0-…
PKM0-25 (+ CL-PKZ0)
ZB32-24
DILM25
DS7-34xSX032N0-…
PKM0-32 (+ CL-PKZ0)
ZB32-32
4)
DILM32
DS7-34xSX041N0-…
NZMN1-M50 / PKZM4-50
ZB65-40 + ZB65-XEZ
DILM50
DS7-34xSX055N0-…
NZMN1-M63 / PKZM4-58
ZB65-57 + ZB65-XEZ
DILM65
DS7-34xSX070N0-…
NZMN1-M80
ZB150-70/KK
DILM80
DS7-34xSX081N0-…
NZMN1-M100
ZB150-100/KK
DILM95
DS7-34xSX100N0-…
NZMN1-M100
ZB150-100/KK
DILM115
DS7-34xSX135N0-…
NZMN2-M160
ZB150-150/KK
DILM150
DS7-34xSX160N0-…
NZMN2-M200
Z5-160/FF250
DILM185
DS7-34xSX200N0-…
NZMN2-M200
Z5-220/FF250
DILM225
1) Used to specify the circuit-breaker required for the specified load cycle.
For other switching cycles (operating frequency, overcurrent, overcurrent time, duty factor), this value changes and must be
modified accordingly.
2) Used to specify the circuit-breaker required for the specified load cycle.
For other switching cycles (operating frequency, overcurrent, overcurrent time, duty factor), this value changes and must be
modified accordingly.
3) (+CL-PKZ0) = optional current limiter
4) The ZB12 or ZB32 overload relay can be fitted directly to a DS7 soft starter.
→
Further information on the overload relays is provided in the Eaton “Main Industrial
Catalog 2010” (HPL0200-2010en-EN) in chapter 6 or on the Internet at:
http://www.eaton.de/EN/EatonDE/ProdukteundLoesungen/Electrical/Kundensupport/index.htm
→
Customer support
→
Catalogues
→
Industrial Switchgear 2011
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...