Eaton Din Rail UPS Advanced User Guide 9340DC—Rev A
9
33..22
A
AC
C W
Wiirriinngg
Figure 5. UPS Input and Output Wiring
Neutral
Neutral
Line
Line
Protective
Earth
Protective
Earth
From Line
To Load
1.
Check that the UPS and the 120V AC Supply are OFF (disconnected) before installation.
2.
Wire the UPS input and output terminals with 194°F (90°C) rated copper wire according to the table below.
Connect the AC input ground terminal to the main supply ground.
UPS Input and Output Wiring Chart
Input Breaker Size
20 Amp for DIN500AC and DIN850AC
Wire Strip Length
0.35 in. (0.9 cm)
Screw Torque
5.3 lb-in (60 N-cm)
Screw
M3.0
Preferred AWG
18 AWG for DIN500AC / 14 AWG for DIN850AC
3.
Charge the UPS battery for a minimum of 8 hours before initial use. The UPS charges its battery whether
the UPS is on or off when it is connected to AC power.
4.
Power ON/OFF UPS:
To turn the UPS ON, press the ON/OFF/TEST button for more than 2 seconds and
release. The UPS LEDs will illuminate and the AC output power will be present
5.
To utilize the additional features and connections, consult the DIN Rail AC UPS Advanced Owner’s
Manual on the Eaton website product page.
Summary of Contents for DIN500AC
Page 1: ...p n 9340DC Revision A Advanced User Guide Eaton DIN Rail AC UPS DIN500AC DIN850AC ...
Page 9: ...6 Eaton Din Rail UPS Advanced User Guide 9340DC Rev A UPS Dimensions ...
Page 13: ...10 Eaton Din Rail UPS Advanced User Guide 9340DC Rev A AC Wiring ...
Page 23: ...9340DCA 9340DC A ...
Page 32: ...6 SAI de riel DIN de Eaton Guia de Usuario Avanzado 9340DC Rev A Dimensiones del SAI ...
Page 46: ...9340DCA 9340DC A ...
Page 55: ...6 Onduleur sur rail DIN Eaton Guide de l utilisateur avancé 9340DC Rev A Dimensions de l ASI ...
Page 69: ...9340DCA 9340DC A ...