Eaton Digitrip RMS 910 Instruction Leaflet Download Page 3

3

Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

List of Figures

Description 

 

 

 

 

           Page

Figure 1 . Digitrip RMS 910 Trip Unit Type LSIG with Rating Plug .  .  .  . 5
Figure 2 . RMS Digitrip 910 Trip Unit - Block Diagram .  .  .  .  .  .  .  .  .  .  .  .  . 6
Figure 3 . Digitrip RMS 910 Type Ll .    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
Figure 4 . Digitrip RMS 910 Type LS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
Figure 5 . Digitrip RMS 910 Type LSI .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
Figure 6 . Digitrip RMS 910 Type LIG .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
Figure 7 . Digitrip RMS 910 Type LSG .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
Figure 8 . Digitrip RMS 910 Type LSIG .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9
Figure 9 . Rating Plug .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .13
Figure 10 . Power/Relay Module .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .14
Figure 11 . Potential Transfer Module .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .14
Figure 12 . Auxiliary Power Module .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .15
Figure 13 . Long Delay Current Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .16
Figure 14 . Long Delay Time Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .16
Figure 15 . Short Delay Current Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .16
Figure 16 . Short Delay Time Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .17
Figure 17 .  Instantaneous Current Settings .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .17
Figure 18 . Ground Fault Current Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .17
Figure 19 . Ground Fault Time Delay Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .18
Figure 20 . Integral Test Panel (Lower Right Corner of Trip Unit) .  .  .  .  .18
Figure 21 . INCOM with Remote Master Computer .  .  .  .  .  .  .  .  .  .  .  .  . 22
Figure 22 . INCOM Network with AEM / BIM .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 23
Figure 23 . INCOM Network with Remote Master Computer and    .  .  

                AEM / BIM .   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 23
Figure A .1 Typical Zone Interlocking (Ground Fault Protection)  .  .  .  . 29
Figure A .2 Typical Zone Interlocking Connections with Two Main 

 

          Breakers (M1, M2) and a Tie Breaker (T) (Short Delay  

 

          Protection) .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 29

List of Tables

Description 

 

 

 

 

           Page

Table 1 .  Digitrip RMS 910 Protection Functions .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 7
Table 2 .  Digitrip RMS 910 Information Functions .   .  .  .  .  .  .  .  .  .  .  .  .  . 11
Table 3 .  Digitrip RMS 910 Trip Unit Message Codes and 

 

        their Meanings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 12

Table 4 .  Ground Fault Current Settings .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 17
Table 5 .  Digitrip RMS 910 Protection Functions .   .  .  .  .  .  .  .  .  .  .  .  .  .  . 25

Summary of Contents for Digitrip RMS 910

Page 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Page 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Page 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Page 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Page 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Page 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Page 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Page 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Page 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Page 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Page 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Page 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Page 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Page 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Page 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Page 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Page 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Page 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Page 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Page 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Page 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Page 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Page 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Page 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Page 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Page 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Page 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Page 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Page 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Page 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: