Eaton Digitrip RMS 910 Instruction Leaflet Download Page 15

15

Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

Following a circuit breaker TRIP operation, the display window 

indicates the reason for trip, using coded messages such as, INST 

(Instantaneous Trip), LDT (Long Delay Trip) etc .  As with the ALARM 

function, press and release the "STEP" push-button to delete the 

reason for trip message and the display window will then show the 

values of current at the time of trip (see Notes (1), (2), and (3) under 

Table 3) .  The values remain in memory, and the "red" reason for Trip 

LED (see Figures 1 and 3 through 8) remains lighted, until the Trip 

Unit is reset by pressing and releasing the "TRIP RESET push-button 

in the lower right corner of the Trip Unit (see Figure 1) .

otee:

N

After a trip condition, RECORD all Values of interest and note which 

"RED" LEDs are lighted .  Correct the cause of the overload or fault BEFORE 

YOU RESET the Trip Unit to avoid repeated tripping .

The LOCKOUT after trip feature requires the Trip Unit to be reset 

before the breaker can be closed again .
For examples of how to interpret the display after an overload and 

after a short-circuit, see Appendix B .

Figure 12. Auxiliary Power Module.

1.2.1.1  ROM Error ... See I.L.

If the message, "ROM Error .  .  . See I .L .", scrolls across the display 

window, it means that a non-fatal error has been detected some-

where in the Trip Unit's non-volatile memory .  The Trip Unit will still 

function to protect the circuit, but the calibration may be degraded 

by a few percent .  The scrolling message will not remain in the win-

dow constantly but is repeated periodically to remind you to replace 

the Trip Unit .

1.3  Frame Rating, Sensor Rating (Where Applicable) and 

Rating Plugs

The 

Frame Rating

 of a circuit breaker is the maximum RMS cur-

rent it can carry continuously .  The maximum Short-Circuit Current 

Ratings of the circuit breaker are usually related to the Frame Rating 

as well .
It is often times desirable to be able to choose a current value 

(I

n

)

less than the full frame rating, to be the basis for the circuit break-

er's protection functions, without affecting its short-circuit current 

capability .  For the Digitrip RMS 910 Trip Unit the maximum continu-

ous current (I

n

) is set by the 

Rating Plug

 (and/or 

Current Sensors

where applicable) - see Section 6 for specific instructions for your 

circuit breaker type .
The 

(Current) Sensor Rating

 (where applicable) is the maximum 

RMS current the circuit breaker can carry with the specified current 

sensors installed .  The Sensor Rating can be the same or less than 

the Frame Rating, but not greater .
The 

Rating Plug

 (see Figure 9) fits into a special cavity to complete 

the Trip Unit (see Figure 1) .

CAUTION

BEFORE YOU FIT THE RATING PLUG INTO THE TRIP UNIT, BE SURE TO CHECK THAT 

THE BREAKER TYPE AND FRAME RATING (OR SENSOR RATING IF APPLICABLE), 

MATCH THOSE PRINTED ON THE RATING PLUG COVER.  INSTALLING A RATING PLUG 

THAT DOES NOT MATCH THE BREAKER TYPE AND FRAME RATING (OR SENSOR 

RATING, IF APPLICABLE), CAN PRODUCE SERIOUS MIS-COORDINATION AND/OR 

FAILURE OF THE PROTECTION SYSTEM.

After installing the Rating Plug, press and release the "TRIP RESET" 

push-button to turn off any illuminated LEDs .  The purpose of the 

rating plug is to set the value of I

n

, the basis for the Trip Unit protec-

tion function current settings (see Section 3 for details) .  Each circuit 

breaker frame rating represents the maximum current it can carry 

continuously .  However for proper coordination of over-current pro-

tection, it is often desirable to choose different levels of I

n

 for differ-

ent circuit breakers of the same frame rating .  An assortment of rat-

ing plugs with different I

n

 values is available for each breaker frame 

rating (see circuit breaker instruction leaflet supplements listed in 

Section 6) to give the user flexibility to change the value of I

n

 with-

out having to change the primary current sensors on the breaker .  

By changing the rating plug, the User can easily change the range 

of current protection settings without having to remove the circuit 

breaker from its enclosure .
For example, if one expects a circuit to carry 600 A initially, but 

then increase to 1400 A in the future, one could initially install 1600 

A cables and a 1600 A breaker frame with the Trip Unit rating plug 

whose I

n

 = 800 A .  Then later on when the additional load is ready 

to come on line, the rating plug could be exchanged for one with I

n

 

= 1600 A, without having to remove the breaker from its enclosure .  

The available settings would give the following choices:
Long Delay Setting
  I

r

 = I

n

 x:  .5   .6   .7   .8   .85   .9   .95  1 .0

Plug I

n

 =800 A

 

LDPU I

r

 = : 400  480  560  640  680  720  760  800 A

Plug I

n

 = 1600 A

 

LDPU I

r

 = : 800  960  1120  1280  1360  1440  1520  1600 A

otee:

N

Rating plugs from Digitrip models 500 / 600 / 700 / 800 CANNOT be 

used with model 910 Trip Units .  The connection pins are located in different 

positions, so one cannot accidentally use the incorrect type of plug .

Rating Plugs for the Digitrip RMS 910 Trip Units are marked for, and 

may be applied on both 50 and 60 Hz systems .
Rating plugs have two current ratings listed on their covers (see 

Figure 9) .

• 

The "Must Use With Frame Rated" current value (or "Sensor 

Rated", if applicable),

and

• 

" I

n

 (rated I)=" current value .

This latter value (I

n

) is the basis for the Trip Unit current settings:

• 

The instantaneous and Ground Current Settings (if applicable) are 

multiples of (I

n

) (see Sections 3 .6 and 3 .8 .) .

• 

The Long Delay Current Setting, 

I

r

  is a multiple of (I

n

) .  Long 

Delay Current Setting = 

I

r

 = LD x (I

n

) (see Section 3 .2 .) .

• 

The Short Delay Current Setting (if provided) is a multiple of 

I

r

 

which in turn is a multiple of (I

n

) .  Short Delay Current Setting = 

SD x 

I

r

 = SD x LD x (I

n

) (see Section 3 .4) .

If the rating plug is missing or not well connected, then the display 

will show "PLUG" and the instantaneous / override LED will be 

lighted .  If the circuit breaker is closed, it will trip; if it is open, it will 

remain trip-free, as long as 120 Vac control power is available to the 

Power / Relay Module .   

Even if control power is lost, and the rating plug condition is not cor-

rected, as soon as the three-phase current through the circuit break-

er reaches 20% (40% if single-phase current) of the frame / current 

Plug for 120Vac 

Receptacle

Trip Unit Connector (Fits into Keyed 

Cavity in Top Right Corner of Trip 

Unit . See Figure 1)

Summary of Contents for Digitrip RMS 910

Page 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Page 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Page 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Page 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Page 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Page 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Page 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Page 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Page 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Page 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Page 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Page 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Page 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Page 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Page 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Page 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Page 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Page 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Page 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Page 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Page 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Page 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Page 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Page 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Page 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Page 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Page 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Page 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Page 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Page 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: