Eaton Digitrip RMS 910 Instruction Leaflet Download Page 21

21

Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

4.4.1  Not Tripping the Breaker

1 .  Place the "TEST AMPS" selector switch (see Figure 20) in one of 

the six "No Trip" test settings, i .e ., 1, 2, 3, 8, or 10 x I

n

, or GF .

2 .  Press and release the (Black) "TEST push-button - the test starts 

when the push-button is released, and the 

elapsed time will 

be displayed

 in the window .  When the timer stops, the lighted 

"RED" cause of trip LED indicates the protection function which 

operated .

3 .  Should any of the various protection settings be less than the 

selected "No Trip" test value, then the LED related to that func-

tion will turn on signifying successful completion of the test 

action .

otee:

N

During the long delay tests the Long Delay LED flashes "RED" .

4 .  Reset the Trip Unit by pressing and releasing the "TRIP RESET" 

push-button; all LEDs lighted by the "No Trip" test action should 

turn "OFF, and the display will again show the value of the cur-

rent through the breaker .  In the event that no one resets the Trip 

Unit after a test, it will wait for about three (3) hours, and then it 

will automatically revert back to its pretest status .

4 .4 .2  Tripping the Breaker

WARNING

CIRCUIT BREAKER OPERATING MECHANISMS OPEN AND CLOSE THE MOVING 

PARTS VERY FAST, AND WITH VERY HIGH ENERGY.  TOUCHING THE MOVING PARTS 

DURING TEST OPERATIONS CAN CAUSE INJURY.  KEEP CLOTHING, HANDS, FEET, 

AND OTHER PARTS OF YOUR BODY WELL AWAY FROM ALL MOVING PARTS DURING 

TESTING.  FOLLOW THE INSTRUCTIONS GIVEN FOR TESTING YOUR SPECIFIC TYPE 

OF CIRCUIT BREAKER, FOUND IN THE APPROPRIATE INSTRUCTION LEAFLET LISTED 

IN SECTION 6.

1 .  Make sure that the circuit breaker is carrying no current (see 

CAUTION notes under Section 4 .1) .

otee:

N

In the event it is decided to perform a "Breaker Trip Test" while load cur-

rent is flowing, make sure the circuit breaker is carrying no more than 50% of 

the Long Delay Current Setting 

I

r

 .  The Trip Unit will NOT execute your instruc-

tions to Test itself, when the load current exceeds 50% of 

I

r

 .

2 .  Place the "TEST AMPS" selector switch (see Figure 20) in either 

the "6T (or "GFT) position .

3 .  Press and release the (Black) "TEST push-button (see Figure 20) - 

the test starts when the push-button is released and the elapsed 

time is displayed in the window .

4 .  At least one of the various protection settings will be less than 

"6x I

n

", and the circuit breaker will trip, the LED related to that 

function will light "RED", and the reason for TRIP code will appear 

in the display window (see Table 3 for Code meanings) .  If the 

"STEP" push-button is pressed and released at this point, the 

"TEST current value will be shown in the display window, not the 

actual current flowing in the breaker .

5 .  Reset the Trip Unit by pressing and releasing the "Trip Reset" 

push-button (see Figure 20) .  All LEDs lighted by the "Trip" test 

action should turn "OFF, and the display window will again show 

the value of current flowing in the breaker .

4.5  Testing the Back-up Battery (Inside the Rating Plug)

The battery has no part in the protection function of the Trip Unit .
The battery is provided only to maintain the "RED" LED indication of 

the cause of TRIP in the Digitrip RMS 910 Trip Unit, when external 

control power to the Power / Relay Module is not available .  The 

battery is located in the rating plug along with a battery check push-

button and a green battery check LED (see Figure 9) .

4.5.1  Back-up Battery Check

The battery is a long life, lithium photo type unit .  The status of the 

battery can be checked at any time .  Press and hold the "battery 

check push-button and observe the "Green" LED as shown in Figure 

9 .  If the battery check LED does not light "Green", replace the bat-

tery .  The condition of the battery has no effect on the protection 

function of the Trip Unit .  Even with the battery removed, the unit 

will still trip the breaker in accordance with its settings .  If however, 

control power is lost and the battery is dead, the cause of TRIP LED 

will not be lighted "RED" .

4.5.2  Replacing the Back-up Battery

The battery can be easily replaced from the front of the Trip Unit by 

lowering the hinged cover of the rating plug as shown in  

Figure 9 .  The battery can then be removed by pulling the battery 

tab as shown in Figure 9 .  After the battery is replaced (or after an 

Auxiliary Power Module is plugged into the Trip Unit), one or more of 

the cause of Trip LED'S may be illuminated .  It is necessary to press 

and release the "TRIP RESET button to turn off any of the LEDs that 

may be illuminated .  Failure to do so can cause the battery to run 

down again .  The Trip Unit will then be ready to indicate the next 

cause of trip .

otee:

N

The battery can be replaced at any time, even while the circuit breaker 

is in service, without affecting the operation of the circuit breaker or its pro-

tection function .

CAUTION

CARE SHOULD BE EXERCISED WHEN REPLACING THE BATTERY TO INSURE 

THAT THE CORRECT POLARITY IS OBSERVED.  POLARITY MARKINGS ARE 

VISIBLE ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS 

INDICATED IN FIGURE 9.  IF THE BATTERY IS INSERTED WITH INCORRECT 

POLARITY, AND IF THE 120 VAC CONTROL POWER TO THE POWER RELAY 

MODULE IS LOST, THEN, AFTER AN OVER CURRENT OR SHORT-CIRCUIT 

TRIP, NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE 

TRIP.

The replacement battery should be the same type or equivalent .  

Acceptable 3 .0 volt lithium batteries may be obtained as type desig-

nation CR 1/3N or DL 1/3N .

Summary of Contents for Digitrip RMS 910

Page 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Page 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Page 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Page 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Page 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Page 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Page 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Page 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Page 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Page 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Page 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Page 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Page 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Page 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Page 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Page 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Page 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Page 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Page 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Page 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Page 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Page 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Page 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Page 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Page 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Page 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Page 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Page 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Page 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Page 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: