![Eaton DeviceNet E50DNA Installation Instructions Manual Download Page 8](http://html1.mh-extra.com/html/eaton/devicenet-e50dna/devicenet-e50dna_installation-instructions-manual_4028987008.webp)
Effective 9/97
Printed in U.S.A.
111032 Rev --
Cutler-Hammer
720 80th Street SW
Everett, WA 98203-6299
www.cutlerhammer.eaton.com
Page 8
APPENDIX: ELECTRONIC DATA SHEETS
(Continued)
Diagnostic Object - Class 198 (C6
HEX
), Instance 1
Attribute
Attribute ID
Access
Number of Faults
1
Get
Fault List
2
Get
Overwrite (0 = preserve oldest faults)
3
Get/Set
(1 = preserve newest faults)
Timestamp (0..65535)
4
Get/Set
Resolution (0..65535 mS)
5
Get/Set
Maximum Number of Faults (8)
6
Get
The Fault List is accessible via the
Get Member service. Each
member has the following structure:
Parameter
Data Type
Class
UINT
Instance
UINT
Error Code
USINT
Additional Error Code
USINT
Status
UINT
Timestamp
UINT
Test Object - Class 199 (C7
HEX
), Instance 1
Attribute
Attribute ID
Access
Power OK
5
Get
LED Disable
6
Get/Set
SOFTWARE TIMING
The E50 is not capable of responding to all DeviceNet messages at all
baud rates if multiple messages are sent in rapid succession. For
best results, a master should wait for a response to a previous
request before sensing a subsequent request.
HARDWARE SPECIFICATIONS
DeviceNet Wiring Connections
V+ Power
Operating range: 11..27 V
Protected range: -30..30 V referenced against V-
V-
Common
CH CAN high
Protected range: -30..30 V referenced against V-
CL CAN low
Protected range: -30..30 V referenced against V-
D
Drain
Still Need Help?
Contact Cutler-Hammer Advanced Product Support
Phone: 1-800-809-2772
Select 2 for Sensor and Application Assistance
Select 6 for DeviceNet Communication and Configuration Assistance