background image

This Transfer Switch may be equipped with a two posi-
tion Keyed Selector Switch that may be used as a
“Service Disconnect” (Figure 8) or as a “Disconnect”
(Figure 9).  If this Transfer Switch does have the two
position Keyed Selector Switch, refer to IL01602002E
for proper labeling.

Operation of the Two Position Keyed Selector
Switch:

Operation 1: When the keyed Selector Switch is in the
“Energize” position, the Transfer Switch functions nor-
mally when the Source 1/Source 2 Selector Switch is

used (Figure and Figure 9).

Operation 2: To disconnect power from the Load: Turn
the Keyed Selector Switch to the “Disconnect” position
(Figure 10 and Figure 11), then remove the key.  The
Transfer Switch will move to the neutral position and
remain there until the Keyed Selector Switch is returned
to the “Energized” position.

Operation 3: To reconnect power to the Load: Reinsert
the key and turn the Keyed Selector Switch to the
“Energize” position (Figure and Figure 9).  The
Transfer Switch will move to the position indicated by
the Source 1/Source 2 Selector Switch.

IM01602002E

For more information visit: www.cutler-hammer.eaton.com

Instruction Leaflet

Page  

5

Effective: June 2003 

Non-Automatic
Transfer Switch
Quick Start Instructions

Figure 10  Service Disconnect Disconnected

Figure 11 Disconnect Disconnected

Figure 8  Service Disconnect Energized

Figure 9  Disconnect Energized

Disconnected

Position Indicated

by Both Connected

Lights being

Extinguished

Summary of Contents for Cutler-Hammer

Page 1: ...S CAN RESULT IN DEATH SEVERE PERSONAL INJURY OR PROPER TY DAMAGE Step 1 Mount the transfer switch on a flat rigid surface Figure 1 Shim if necessary For seismic mounting requirements check the instruc...

Page 2: ...4 pole transfer switches connect load cables T4 Source 1 or utility supply N4 and Source 2 or genera tor supply E4 Refer to Figure 2 for the location of all parts discussed in this document Load cable...

Page 3: ...ted Light should illuminate Figure 5 Using a voltmeter check for proper system voltage on the nor mal and load terminals Check all phases on a three phase switch Voltage measurements should be taken p...

Page 4: ...operations The range is from 3 60 sec onds Step 5 Move the Selector Switch on the Device Panel to Source 2 Figure 7 The Transfer Switch will move to the Neutral Position delay and then move to the So...

Page 5: ...Figure 10 and Figure 11 then remove the key The Transfer Switch will move to the neutral position and remain there until the Keyed Selector Switch is returned to the Energized position Operation 3 To...

Page 6: ...IM01602002E For more information visit www cutler hammer eaton com Instruction Leaflet Page 6 Effective June 2003 Non Automatic Transfer Switch Quick Start Instructions...

Page 7: ...IM01602002E For more information visit www cutler hammer eaton com Instruction Leaflet Page 7 Effective June 2003 Non Automatic Transfer Switch Quick Start Instructions...

Page 8: ...01602002E ISI June 2003 Eaton Corporation Cutler Hammer business unit 1000 Cherrington Parkway Moon Township PA 15108 4312 USA tel 1 800 525 2000 www cutler hammer eaton com Instruction Leaflet Page 8...

Reviews: