Pub 49004

Page 9

Effective 9/00

Short Circuit Ratings

Soft Starter

Three Phase Short Circuit Rating

Frame Size

240V

480V

600V

S801N  65mm

10KA

10KA

10KA

S801R  110mm

10KA

10KA

10KA

15-Second Ramp, 4 Starts per Hour, 300% Current Limit  @ 40

o

C

Severe Duty Ratings

Severe Duty Ratings are defined as any combination of parameters that exceed the Standard Duty Ratings.

Example;  35-Second Ramp, 5 Starts per Hour, 350% Current Limit @ 40 Deg C Ambient.

Frame

Max

Catalog

Width

Current

Number

230

380-400

440

Volt

Volt

Volt

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

1.0SF

1.15SF

65mm

37

10

18.5      18.5

10         10

10        10

25          20

30

30

S801N37N3S

66

18.5

30         37

20         15

20        20

50          40

60

50

N66N3S

110 mm

105            30

55         59

30         25

40        30

75          60

100           75

S801R10N3S

135            40

63         80

40         30

50        40

100         75

125          100

R13N3S

Three-Phase Motor

hp Rating (60 Hertz)

kW Rating (50 Hertz)

200V

230V

460V

575V

Frame

Max

Catalog

Width

Current

Number

230

380-400

440

Volt

Volt

Volt

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

1.0SF

1.15SF

65mm

22

5.5

10           11

5

5

7.5

5

15           10

20

15

S801N37N3S

42

11

18.5

22          10

10         15

10         30

25

40

30

N66N3S

110 mm

65

15           30

33          15

15         20

15         50

40

50

50

S801R10N3S

80

22           40

45          25

20         30

25         60

50

75

60

R13N3S

Three-Phase Motor

hp Rating (60 Hertz)

kW Rating (50 Hertz)

200V

230V

460V

575V

Cooling

Fans are used to cool the IT Soft Starter. The fans are

turned on when the temperature of any of the thermal

sensors exceeds a preset value. If the temperature is

below this value, the fans will be off.
The fans will also be turned on whenever the IT is started,

stopped, or jogged. The fans will remain on for 15 minutes

to assure the SCRs are adequately cooled prior to the

next start or jog.
If a temperature is sensed above a second preset level,

a Pole Over-Temperature Fault will occur. This fault cannot

be reset until the temperature returns to a safe level.
Note that the fans will only operate if 24 VDC is applied

to the + and – terminals.

CE Conformity

S801N will meet IEC 60947-4-2 and EN60947-4-2

Radiated Immunity Test requirements, except for the

following frequency bands:

80 to 89.2 MHz @ 9 V/m

90.1 to 92 MHz @ 6 V/m

S801R will meet IEC 60947-4-2 and EN60947-4-2

Radiated Immunity Test requirements, except for the

following frequency bands:

90.04 to 92.87 MHz @ 6 V/m

91.9 to 92.8 MHz @ 9 V/m

All manuals and user guides at all-guides.com

Summary of Contents for Cutler-Hammer S801TR

Page 1: ...ll wave power bridge The voltage and current applied to the motor is controlled by varying the thyristor conduction period This in turn controls the torque supplied by the motor After the motor reache...

Page 2: ...0 5 Standard 10 4 1 7 N m 65mm Lockwasher and 15 in lb 2 55 in Flat Washer S801R 1 4 20 x 0 625 Standard 1 4 4 2 8 N m 110mm Lockwasher and 25 in lb 4 33 in Flatwasher Required Mounting Hardware Fram...

Page 3: ...cation as shown To mount the unit use all the hardware specified in Table 1 on page 2 of this leaflet Tighten to the torque specified TO AVOID SHOCK HAZ ARD DISCONNECT ALL POWER BEFORE ANY FUNCTIONS A...

Page 4: ...AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE POURRAIT CAUSER DES DOMMAGES IMPORTANTS AU CONTROLEUR ATTENTION T...

Page 5: ...DAMAGE TO THE CONTROLLER CAUTION APPLIQUER UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE...

Page 6: ...d it will communicate with the CIM and load the program into the Soft Starter Allow the unit 2 seconds to ensure communication checks complete and values are set To verify CIM is operational press Fau...

Page 7: ...41 24V power supply low 42 Timer system fault 43 Watchdog reset occurred 44 PLL DSP 45 Illegal address DSP Effective 9 00 Table 7 Fig 6 Soft Start Control Interface Module CIM TORQUE T2 T1 TORQUE T2...

Page 8: ...40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor kW Rating 50 Hertz hp Rating 60 Hertz 200V 230V 460V 575V 15 Second Ramp 4 Starts per Hour 450 Current Limit 40o C Fra...

Page 9: ...10 30 25 40 30 N66N3S 110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor hp Rating 60 Hertz kW Rating 50 Hertz 200V 230V 460V 575V Cooli...

Page 10: ...ce or start up assistance 24 hours day 7 days week please call 1 800 498 2678 Cutler Hammer Solid State Reduced Voltage Motor Starter Aftermarket Services Technical telephone support Resident service...

Reviews: