Eaton Cutler-Hammer Modbus mMINT Installation And Use Manual Download Page 4

Page 4

I.L. 66A7508H05

Effective September 2003

RS485 Network-A is the non-inverting differential connection
for the Modbus RTU network. RS485 Network-B is the
inverting differential connection for the Modbus RTU network.

Figure 4:  Indicators

5.0  SWITCHES AND INDICATOR LEDS

Refer to 

Figure 4

 to locate the status LED for the mMINT

module. 

Figure 5

 shows the location of the configuration

switches.

5.1  Modbus RS485 Network Rx LED [Green]

The LED will be lighted whenever the module is receiving from
the Modbus RTU network.

5.2  Modbus RS485 Network Tx LED [Green]

The LED will be lighted whenever the module is transmitting on
the Modbus RTU network.

5.3  INCOM Network Rx LED [Green]

The LED will be lighted whenever the module is receiving from
the INCOM network.

5.4  INCOM Network Tx LED [Green]

The LED will be lighted whenever the module is transmitting on
the INCOM network.

5.5  Status LED [Green]

This indicator will be flashing whenever the module is powered
up and the microcontroller is executing instructions. The
flashing rate is approximately 1 second ON / 1 second OFF.
However, detection of a communications error on either the
Modbus or INCOM network will result in an increased flashing
rate approximately ½ second ON / ½ second OFF. The rate
will return to normal when the network's diagnostic reset
subfunction (clear UART or slave counters, respectively) is
processed by the mMINT.  See Section 6.9 and 

Table 6

.

Figure 5: Switches

5.6 INCOM 

100 

 Termination Dip Switch (SW1)

This switch should be moved to the “ON” position only when it
is the last unit in a chain of units or if it is a single unit.

5.7  Modbus RS485 Baud Rate Dip Switch (SW2)

To configure the data transfer rate for the Modbus RTU
network, three switches in dip switch SW2 should be moved to
either the “CLOSE” or the “OPEN” position based on the rate
required. Refer to 

Table 4

. SW2-1 is for mMINT diagnostics.

Baud

SW2-1

SW2-2

SW2-3

1200

X

CLOSE

CLOSE

9600

X

OPEN

CLOSE

19200

X

CLOSE

OPEN

Table 4:  RS485 Baud Rate Switches (Normal)

5.8  Unique mMINT Address (SW2)

The mMINT can be assigned address 247 and 248.  For the
mMINT to respond to a diagnostic query related to address
247 or 248 on the Modbus network, move dip switch SW2-1 to
the “OPEN” position. Refer to 

Table 5

.  Normally, this switch is

in the “CLOSE” position.

Summary of Contents for Cutler-Hammer Modbus mMINT

Page 1: ...ations 6 6 6 Command Data Pass Through 6 6 7 Control of INCOM Product 6 6 8 Energy Format 7 6 9 Supported Diagnostic Sub Functions 8 6 10 Exception Codes 8 7 0 Troubleshooting 9 APPENDIX A 9 Notes 19...

Page 2: ...changes LED indicators for Modbus RS485 transmit and receive communications exchanges Input power for the module from either 120 Vac or 48 to 125 Vdc DIN rail mount package 0 C to 60 C ambient operati...

Page 3: ...twork Make sure that there is twisted pair wire that is recommended for Modbus RTU network use Use shielded twisted pair wire to connect each slave to the Modbus RTU network daisy chain style The pola...

Page 4: ...pproximately 1 second ON 1 second OFF However detection of a communications error on either the Modbus or INCOM network will result in an increased flashing rate approximately second ON second OFF The...

Page 5: ...column of Table 7 or Table 8 can be established for each INCOM product attached to a mMINT Function code 16 1016 is used to load the object assignments for the block of registers The block assignments...

Page 6: ...the configured sub network address accessed through a sub network master addressed at the INCOM main network address All INCOM Routing Address Configuration registers can be reset to their default st...

Page 7: ...ter format is presented in units of Kwatthours and is valid for INCOM products reporting energy in watthours or Kwatthours only Products reporting in units greater than Kwatthours e g Mwatthours could...

Page 8: ...ction exception code 07 NAK is returned If only a partial register is used in the query exception code 84 is returned Sub function No decimal Name in the query use 0 echo query mMINT or INCOM addr 1 r...

Page 9: ...IN rail mounting 3 Control voltage is 120 VAC 20 or 48 125 VDC 4 Connectors are plug in types from Phoenix Contact 5 Terminal Types supplied with module are 3 point 4 point and 5 point Phoenix Contact...

Page 10: ...N demand A 404649 406185 1228 1828 10 x real 3 ph power W 404651 406187 122A 182A 1 x x x x x x reactive 3 ph VAR 404653 406189 122C 182C 1 x x x x x x Power apparent 3 ph VA 404655 406191 122E 182E 1...

Page 11: ...1892 1 x load bearing 1 o C 404757 406293 1294 1894 1 x load bearing 2 o C 404759 406295 1296 1896 1 x auxiliary o C 404761 406297 1298 1898 1 x Temperature device temperature o C 404763 406299 129A 1...

Page 12: ...159 120E 180E 10 x x x x x x x x VBC V 404625 406161 1210 1810 10 x x x x x x x x VCA V 404627 406163 1212 1812 10 x x x x x x x x L L voltage VLLavg Vavg 404629 406165 1214 1814 10 x VAN V 404631 406...

Page 13: ...nt B ph pf 404693 406229 1254 1854 100 x x apparent C ph pf 404695 406231 1256 1856 100 x x Power factor apparent pf 404659 406195 1232 1832 100 x x x x x x K factor K factor 404663 406199 1236 1836 1...

Page 14: ...ed 13 Picked up 14 Phase A Trip 15 Phase B Trip 252 Product Specific Code 252 16 Phase C Trip 253 Product Specific Code 253 17 Neutral Trip 254 Product Specific Code 254 18 Ground Earth Trip 255 Produ...

Page 15: ...lure 4 16 Over Frequency 55 Diagnostic failure 5 17 Current Unbalance 56 Diagnostic failure 6 18 Voltage Unbalance 57 Diagnostic failure 7 19 Apparent Power Factor 58 Diagnostic failure 8 20 Displacem...

Page 16: ...ck 94 Load Bearing Temperature 136 Real Time Clock 95 Auxiliary Temperature 137 High Floating Voltage 96 Winding Temperature 138 Trip Blocked 97 Local Temperature 139 Incomplete Sequence 98 External T...

Page 17: ...er 0 1 18 Reset min max current THD 0 1 19 Reset min max voltage THD 0 1 20 Reset min max per phase power 0 1 22 Reset op count runtime override count 0 1 36 Reset motor data maximum values 0 1 37 Res...

Page 18: ...fer 5 0 4 Cancel ATS test 5 0 5 Go to emergency 5 0 6 Automatic Transfer Switch Control Cancel Go to emergency 5 0 7 Table 12 Control Slave Action Number Definitions continued Register10 Modbus Addres...

Page 19: ...rchaser and Cutler Hammer Inc NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR USAGE O...

Page 20: ...Page 20 I L 66A7508H05 Effective September 2003 Cutler Hammer Pittsburgh PA U S A Printed in U S A...

Reviews: