Page 18
I.L. 66A7508H05
Effective September 2003
Control Group
Definition
Byte2
Byte1
Byte0
Release time-stamped event buffer
3
0
0
Capture waveform
3
0
1
Reset INCOM slave-interface statistics
3
0
2
Reset product-specific statistics
3
0
3
Acknowledge triggered event(s)
3
0
4
Reset sun-network master INCOM statistics
3
0
5
Acknowledge energy-reset
3
0
6
Acknowledge setpoints change buffer
3
0
7
Release time-stamped minor event buffer
3
0
8
System Control
Release time-stamped motor start profile buffer
3
0
9
Activate relay output #X (X=relay number 0-255)
4
1
X
Relay Control
De-activate relay output #X (X=relay number 0-255)
4
2
X
Initiate ATS test
5
0
1
Bypass TDNE/TDEN
5
0
2
Initiate manual transfer
5
0
4
Cancel ATS test
5
0
5
Go to emergency
5
0
6
Automatic
Transfer Switch
Control
Cancel Go to emergency
5
0
7
Table 12: Control 'Slave Action Number' Definitions, continued.
Register
10
Modbus Address
16
Register Definition
R/W
Low
High
Low
High
# of
Regs
10
mMINT (247 or 248 addressed)
Invalid Object Access Configuration
R/W
42001
425345
07D0
6300
1
Floating Pt Data Word Order Configuration
R/W
42002
425346
07D1
6301
1
Fixed Pt Data Word Order Configuration
R/W
42003
425347
07D2
6302
1
INCOM Routing Address Configuration
R/W
42101
0834
2 * 246
INCOM (device addressed)
Mapped Block Of Registers Configuration
R/W
41001
420481
03E8
5000
100
Mapped Block Of Registers Data
R
41201
420737
04B0
5100
4 * 100
Modbus-To-INCOM Query
W
42601
424577
0A28
6000
2
Modbus-To-INCOM Response
R
42701
424833
0A8C
6100
2 * 63
Supervisory Control Query
R/W
42901
425089
0B54
6200
3
Table 13: mMINT Configuration Registers.