IM05805016K
Page 9
Effective October 2007
“CURRENT ERROR”
is displayed if a battery
test has failed during a charge cycle due to any of
the following conditions:
Battery charger output current is greater than the
maximum battery current threshold.
1
Battery charger output current is greater than the
battery charge mode maximum current threshold.
2
Battery charger output current is less than the
battery charge mode minimum current threshold.
Charger Setup: Lead Acid / Ni Cad
DIP switches on the charger can be used to select a
number of options including battery type and
voltage as well as Forced Charging. Options
currently supported for the charger include 12 or
24 Volt Lead Acid and NiCad Batteries.
Lead Acid
To select 12Volt battery charge cycle with Lead
Acid batteries set all DIP switches to the OFF
position.
To select 24Volt battery charger cycle with Lead
Acid batteries, set DIP switch 3 to the ON position
and all other DIP switches to the OFF position.
NiCad
To select 12Volt battery charger with NiCad
batteries, set DIP switch 6 to the ON position and
all other DIP switches to the OFF position.
To select 24Volt battery charger cycle with NiCad
batteries, set DIP switches 3 and 6 to the ON
position and all other DIP switches to the OFF
position.
Forced Charging
There is provision for the battery chargers to
provide a forced charge to the batteries.
The Forced Charge function will only activate
immediately after applying power to the charger
with DIP Switch 8 in the ON position and a battery
connected.
When the charger is in the forced charge mode, it
will attempt to recover a battery by delivering
10 amps. If the battery does not reach the
minimum battery voltage (8 volts for a 12 volt
system; 18 volts for a 24 volt system) within 5
minutes, the recovery attempt will terminate. Once
the battery reaches it's minimum battery voltage,
the normal charge sequence will commence.
Forced charging will only occur once per battery
charger power cycle.
Installation / Mounting
Two chargers are direct mounted to the back pan.
A retrofit kit consisting of a retrofit mounting
plate, single battery charger and wire connection
terminals is available for retro-fitting previous
models. Refer to the Renewal Parts List
PL05805008K.
Specifications
Voltage Input: 90 - 240VAC - Auto detect
Voltage Output: 12 - 24VDC-DIP switch selectable
Hertz: Operates on 50 / 60Hz
Operating Temperature: 0 to 55 degrees C
9.
Operating Temperature
The operating temperature range of the FD100 is:
-20°C to 55°C.
1 - Refer to Appendix A: Table 1
2 - Refer to Appendix A: Table 2
1
ON
OFF
2
3
4
5
6
7
8
12 Volt - Lea d Acid
12 Volt Lead Acid
ON
OFF
1
ON
OFF
2
3
4
5
6
7
8
24 Volt - Lea d Ac id
24 Volt Lead Acid
ON
OFF
1
ON
OFF
2
3
4
5
6
7
8
12 Volt - NiCa d
12 Volt - NiCad
ON
OFF
1
ON
OFF
2
3
4
5
6
7
8
24 Volt - NiCa d
24 Volt - NiCad
ON
OFF
1
1
1
1
ON
ON
ON
ON
OFF
OFF
OFF
OFF
2
2
2
2
3
3
3
3
4
4
4
4
5
5
5
5
6
6
6
6
7
7
7
7
8
12 Volt - Lea d Acid
12 Volt - NiCa d
24 Volt - Lea d Acid
24 Volt - NiCa d
8
8
8
24 Volt - NiCad
ON
OFF
12 Volt - NiCad
ON
OFF
12 Volt Lead Acid
ON
OFF
24 Volt Lead Acid
ON
OFF
Summary of Contents for Cutler-Hammer FD100
Page 2: ......