I.B. 17555C
Effective November 1999
Page B3
TABLE B-2 DT3010 AND DT3020 SPECIFICATION AND TEST SUMMARY (CONTINUED)
CURRENT INPUTS:
•
Cts:
5A Secondary
•
Ct Burden:
See Burden Curves Figures 8 & 9
<0.04 ohm @ Rated Current(5A)
<1.0 VA @ Rated Current(5A)
•
I
n
:
5A(Secondary) or CT (Primary)
•
Saturation:
30 x I
n
•
Ct Thermal Rating:
10A continuous
500A for 1 Second
CT(PRIMARY) SETTINGS AVAILABLE:
•
Phase & Ground:
10/25/50/75/100/150/200/250/300/
400/500/600/630/800/1000/1200/
1250/1500/1600/2000/2400/2500/
3000/3200/4000/5000
CURRENT MONITORING:
•
True RMS Sensing:
3-Phase and Ground
•
Display Accuracy:
+1% of Full Scale [I
n
] from 0.04xI
n
to 1xI
n
+2% of Full Scale [I
n
] from 1xI
n
to 2xI
n
•
Amp Demand:
Average demand over
5 minute sampling window
•
High Load Threshold:
85% of Long Delay or Inverse
Time Overcurrent Setting
OUTPUT TRIP CONTACTS:
(Trip OC/Comm, Trip Inst, & Comm Close)
•
Momentary:
Make 30A ac/dc for 0.25 sec
Break 0.25A @ 250Vdc
Break 5A @ 120/240Vac
•
Continuous:
5A @ 120/240Vac
5A @ 30Vdc
•
Meets ANSI C37.90, Paragraph 6.7
ENVIRONMENT:
•
Environment:
Indoor Use Only, Pollution Degree II,
Altitude 2,500m, Installation Category II
•
Mounting Location:
Device should be positioned near the
main disconnect
•
Operating Temperature: -30 to +55 Degrees Celsius
•
Operating Humidity:
0 to 95% Relative Humidity
[Non-Condensing]
•
Storage Temperature:
-40 to +70 Degrees Celsius
COMMUNICATIONS:
•
PowerNet Compatible / Built-in INCOM
•
Data Rate is 1200 or 9600 Baud
•
Set INCOM address from front panel
PHASE OVERCURRENT PICKUP RANGES:
•
Inverse Time
Overcurrent Setting:
(0.2 to 2.2) x I
n
[29 settings]
•
Short Delay Setting:
(1 to 11) x In, None[25 settings]
•
Instantaneous Setting: (1 to 25) x In, None[30 settings]
GROUND OVERCURRENT PICKUP RANGES:
•
Inverse Time Overcurrent
•
Setting:
(0.1 to 2.0) x In [26 settings]
•
Short Delay Setting:
(0.1 to 11) x In, None [45 settings]
•
Instantaneous Setting: (0.5 to 11) x In, None [33 settings]
TIME DELAY SETTINGS:
•
Inverse Time Overcurrent
Time Multiplier:
It, I
2
t, I
4
t Curve: 0.2 to 40[48 Settings]
Flat: 0.2 to 2.0[21 Settings]
ANSI (all): 0.1 to 5.0[50 Settings]
IEC (all): 0.025 to 1.00[40 Settings]
•
Short Delay Time:
0.05 to 1.5 sec.[22 Settings]
TIMING ACCURACY:
•
Inverse Time Overcurrent
Time:
+10% @ >1.5 x Pickup
•
Short Delay Time:
+50ms
AUXILIARY RELAYS:
(Protection Off Alarm and Trip Alarm)
•
Make/Break:
5A @ 120/240Vac & 30Vdc
•
Continuous:
5A @ 120/240Vac
5A @ 30Vdc
ADDITIONAL TESTS:
•
Dielectric Strength:
Current Inputs: 3,000Vac for 1 minute
Phase to Phase
•
Siesmic Test:
Meets requirements for UBC and
California Building Code Zone 4
ZPA = 3.5
ZONE SELECTIVE INTERLOCKS:
•
Phase:
Inverse Time Overcurrent and
Short Delay
•
Ground:
Inverse Time Overcurrent and
Short Delay
NOTES: 1.For Ground Pickup < 0.2pu; Time Tol 15%.
Summary of Contents for Cutler-Hammer Digitrip 3000
Page 18: ...I B 17555C Effective November 1999 Page 12 Fig 2 1 Typical Communications Wiring Diagram...
Page 27: ...I B 17555C Effective November 1999 Page 21 Fig 3 1 Digitrip 3000 Typical Wiring Diagram...
Page 36: ...I B 17555C Effective November 1999 Page 30 Fig 3 11 Local Programming Sequence Flow Chart...
Page 37: ...I B 17555C Effective November 1999 Page 31...
Page 52: ...I B 17555C Effective November 1999 Page 46 Fig 7 5 Short Delay Phase Curves SC 5394 92B...
Page 54: ...I B 17555C Effective November 1999 Page 48 Fig 7 7 Instantaneous Curves SC 5396 92B...
Page 59: ...I B 17555C Effective November 1999 Page 53 Fig 7 12 Short Delay Ground Curves SC 5403 92B...
Page 60: ...I B 17555C Effective November 1999 Page 54 Fig 7 13 ANSI Moderately Inverse Curves SC 6685 96...
Page 61: ...I B 17555C Effective November 1999 Page 55 Fig 7 14 ANSI Very Inverse Curves SC 6686 96...
Page 62: ...I B 17555C Effective November 1999 Page 56 Fig 7 15 ANSI Extremely Inverse Curves SC 6687 96...
Page 63: ...I B 17555C Effective November 1999 Page 57 Fig 7 16 IEC A Moderately Inverse Curves SC 6688 96...
Page 64: ...I B 17555C Effective November 1999 Page 58 Fig 7 17 IEC B Very Inverse Curves SC 6689 96...
Page 65: ...I B 17555C Effective November 1999 Page 59 Fig 7 18 IEC C Extremely Inverse Curves SC 6690 96...
Page 66: ...I B 17555C Effective November 1999 Page 60 Fig 7 19 IEC D Flat Curves SC 6691 96...
Page 68: ...I B 17555C Effective November 1999 Page 62...
Page 73: ...I B 17555C Effective November 1999 Page A5 Fig A 7 DT3001 Typical Wiring Diagram...
Page 76: ...I B 17555C Effective November 1999 Page A8...
Page 81: ...I B 17555C Effective November 1999 Page B5 Fig B 2 Digitrip 3010 3020 Dimensions Inches...
Page 83: ...I B 17555C Effective November 1999 Page B7 Fig B 3 Digitrip 3010 3020 Typical Wiring Diagram...
Page 89: ...I B 17555C Effective November 1999 Page B13...
Page 90: ...I B 17555C Effective November 1999 Page B14...