I.B. 17555C
Effective November 1999
Page 35
SECTION 5: INSTALLATION, STARTUP AND
TESTING
5-1
INTRODUCTION
This section describes mounting, wiring, startup and mis-
cellaneous testing details associated with the Digitrip
3000 Protective Relay.
WARNING
INSURE THAT THE INCOMING AC POWER AND FOR-
EIGN POWER SOURCES ARE TURNED OFF AND
LOCKED OUT BEFORE PERFORMING ANY WORK
ON THE DIGITRIP 3000 TRIP UNIT OR ITS ASSOCI-
ATED EQUIPMENT. FAILURE TO OBSERVE THIS
PRACTICE COULD RESULT IN SERIOUS INJURY,
DEATH AND/OR EQUIPMENT DAMAGE.
5-2
PANEL PREPARATION
This section describes the panel preparation and mount-
ing of the Digitrip 3000 Protective Relay.
5-2.1 CUTOUT
Since the Digitrip 3000 Protective Relay is typically
mounted on a cabinet door, it is necessary to prepare a
cutout in which it will be placed. The dimensions for this
cutout, along with the location of the six mounting holes,
are shown in Figure 5-1. Before actually cutting the
panel, be sure that the required 3-dimensional clear-
ances for the relay chassis allow mounting in the desired
location. Digitrip 3000 Protective Relay dimensions are
shown in Figure 5-2.
It is necessary to hold the tolerances shown when mak-
ing the cutouts and placing the holes for the mounting
screws. In particular, the horizontal dimensions between
the center of the mounting holes and the vertical edge of
the cutout must be within 0 and +0.050 in. (0.13 cm).
5-2.2 MOUNTING
Do not use a tap on the face of the relay since this will
remove excessive plastic from the holes, resulting in less
threaded material to secure the relay to it mounting
panel.
Place the Digitrip 3000 Protective Relay through the cut-
out in the panel. Be sure the Operator Panel faces out-
ward. Use the 0.38 in. (0.9 cm) long screws included with
the relay to mount the unit on a single-thickness panel.
Fig. 5-1
Cutout Dimensions (Inches)
Be sure to start the screws from INSIDE the panel, so
they go through the metal first.
5-3
REPLACING DIGITRIP MV WITH DIGITRIP 3000
The Digitrip 3000 can be installed as a direct replace-
ment for the Digitrip MV with proper DIP switch settings
as shown in Table 5.1. The five following important points
must be considered when configuring a Digitrip 3000 to
function as a Digitrip MV.
1.
DIP switches S1, S2 and S3 must be set to the OFF
position.
2.
The selected curve shape must be It, I
2
t, I
4
t or FLAT.
3.
The phase and ground curves must be set the same.
4.
The CT settings must be set from the front panel.
They cannot be set via IMPACC.
5.
The thermal curves only are used for system coordi-
nation.
Summary of Contents for Cutler-Hammer Digitrip 3000
Page 18: ...I B 17555C Effective November 1999 Page 12 Fig 2 1 Typical Communications Wiring Diagram...
Page 27: ...I B 17555C Effective November 1999 Page 21 Fig 3 1 Digitrip 3000 Typical Wiring Diagram...
Page 36: ...I B 17555C Effective November 1999 Page 30 Fig 3 11 Local Programming Sequence Flow Chart...
Page 37: ...I B 17555C Effective November 1999 Page 31...
Page 52: ...I B 17555C Effective November 1999 Page 46 Fig 7 5 Short Delay Phase Curves SC 5394 92B...
Page 54: ...I B 17555C Effective November 1999 Page 48 Fig 7 7 Instantaneous Curves SC 5396 92B...
Page 59: ...I B 17555C Effective November 1999 Page 53 Fig 7 12 Short Delay Ground Curves SC 5403 92B...
Page 60: ...I B 17555C Effective November 1999 Page 54 Fig 7 13 ANSI Moderately Inverse Curves SC 6685 96...
Page 61: ...I B 17555C Effective November 1999 Page 55 Fig 7 14 ANSI Very Inverse Curves SC 6686 96...
Page 62: ...I B 17555C Effective November 1999 Page 56 Fig 7 15 ANSI Extremely Inverse Curves SC 6687 96...
Page 63: ...I B 17555C Effective November 1999 Page 57 Fig 7 16 IEC A Moderately Inverse Curves SC 6688 96...
Page 64: ...I B 17555C Effective November 1999 Page 58 Fig 7 17 IEC B Very Inverse Curves SC 6689 96...
Page 65: ...I B 17555C Effective November 1999 Page 59 Fig 7 18 IEC C Extremely Inverse Curves SC 6690 96...
Page 66: ...I B 17555C Effective November 1999 Page 60 Fig 7 19 IEC D Flat Curves SC 6691 96...
Page 68: ...I B 17555C Effective November 1999 Page 62...
Page 73: ...I B 17555C Effective November 1999 Page A5 Fig A 7 DT3001 Typical Wiring Diagram...
Page 76: ...I B 17555C Effective November 1999 Page A8...
Page 81: ...I B 17555C Effective November 1999 Page B5 Fig B 2 Digitrip 3010 3020 Dimensions Inches...
Page 83: ...I B 17555C Effective November 1999 Page B7 Fig B 3 Digitrip 3010 3020 Typical Wiring Diagram...
Page 89: ...I B 17555C Effective November 1999 Page B13...
Page 90: ...I B 17555C Effective November 1999 Page B14...