background image

P51923

 Rev 01

Effective: April 2007

Page 2

Questions? Call our Sensor Application Engineers at (800) 426-9184.

4,000 ohms should provide a load of 30 mA at 120V AC, or a night light 
bulb of 4 watts should relate to 33 mA. With the load energized and 
passing through the sensing aperture, turn the potentiometerclockwise 
until the sensor trips. Then, back one-eighth of a turn and the setpoint 
should be correct. 

When used with an external current transformer (CT), the sensor will 
be set to trip at a point much lower than without the CT.  This set point 
adjustment should be done with the load passing through the CT in that 
application.

POWER SUPPLY NOTES

All low-current ground-fault sensors are sensitive devices that require 
reasonable care in system design to avoid false trips caused by high 
electrical noise levels. Keep in mind that the best way to reduce noise in 
a system is to suppress it at its source. 

•  Keep the sensor power isolated from noisy circuits
•  Do not power the sensor with the same circuit that switches 

contactors or other high current inductive loads

SYSTEM GROUNDING

Good design practice and code require that all AC power systems be 
grounded. The EGF Series sensors are designed to work on grounded 
AC power systems. They may not operate properly on ungrounded 
systems.

SPECIFICATIONS

Specifi cation

Value

Power Supply

120V AC (Operates from 66-132V)
24V AC/DC (Operates from 19.2-28.8V)

Voltage Range

Up to 1,500V AC (Monitored Circuit)

Power Consumption

2.5W

Output

Latching Electromechanical Relay
Normally Open Models Latch Closed Upon Sensed Fault Current
Normally Closed Models Latch Open Upon Sensed Fault Current

Output Rating

1.0A @ 120V AC
2.0A @ 30V AC

Response Time

At 5% Over Setpoint: 200 ms
At 50% Over Setpoint: 60 ms
At 500% Over Setpoint: 15 ms

Setpoint Range

Selectable by Model
   Fixed Setpoints: 50, 100 mA
   Adjustable Setpoints: 5, 10, 30 mA (By Jumper)

Setpoint Adjustment

See “Adjust Setpoint” in “Operation” Section

Frequency Range

50-400Hz (Monitored Circuit)

Housing

UL94 V0 Flammability Rated

Dimensions

Case: 2.5 in. H x 2.8 in. W x 1.5 in. D (64x71x38mm)
Aperture: 0.75 in. (19mm)

LED

Green = Power Supply Energized
Red = Relay Has Operated

Environmental

Operating Temperature: +5 to +158° F (-15 to +70° C)
Humidity: 0-95% RH, Non-Condensing

Approvals

UL Recognized

490050021

WIRING 

Use up to 14 AWG copper wire and tighten terminals to 4.5 inch-
pounds torque. See diagram below.

Power

Connect power wiring to Terminals 1 and 2. Be sure that the power 
supply matches the power rating on the sensor label.

Output

Connect output wiring to Terminals 3 and 4.

Reset Switch

Connect a momentary dry contact to the Reset Terminals 5 and 6. Limit 
wire run to 200 feet of 18 AWG or larger wire.

Momentary Reset

Only close the reset terminals momentarily—the sensor will not work 
properly if the reset terminals are closed (shorted) continuously. Limit 
wire run to 200 feet of 18 AWG or larger wire.

Parallel Reset Connection

Multiple sensors may be connected to the same reset switch in parallel. 
Only the sensors that have detected a fault and have latched will 
be reset. A sensor will not reset unless the fault has dropped below 
setpoint.

OPERATION

The EGF Series latching ground fault sensors operating in one of two 
states: Reset or Latched. If control power is removed, the sensor 
remains in it’s last state (latched or reset).

Reset

The sensor has not detected a fault and the output is in the “normal” 
position. For Normally Open (N.O.) sensors, the contact is normally 
open in the reset condition. For Normally Closed (N.C.) sensors, the 
contact is normally closed in the reset position.

Latched

Upon detecting a fault or when the TEST switch is pressed, the output 
will switch and “latch.” The output will remain latched until the ground 
fault is removed and the output is reset by a momentary dry contact on 
Terminals 5 and 6.

Testing

To test operation, gently press the TEST button. This simulates a fault 
and tests the internal switching circuits. After the test is complete, 
reset the sensor with a momentary dry contact on Terminals 5 and 6. 

CAUTION: Any circuit connected to the sensor will be operated.

Adjusting Setpoint

While not as precise as having it set at the factory, the setpoint can be 
adjusted in the fi eld. See wiring diagram for location of potentiometer. 
The best way to adjust the trip point is to develop a load of the 
magnitude at which you want the sensor to trip. A resistor of 

Red Status LED (On When Tripped)

Setpoint Adjustment
(Located Under Label)

Test Button 

(Caution: Will Activate Output Relay)

External Reset Button (5 and 6)

Output (3 and 4)

Power Supply Input (1 and 2)

Power (Green) LED
(On if Power is Applied)

1

2

3

4

5

6

G

R

TEST

Reviews: